50 Connect Devices WAGO-I/O-SYSTEM 750750-493 3-Phase Power Measurement ModuleManualVersion 1.2.0Pos : 75 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Ansc hließ en/Ger äte ansc hließen - Ü bers chrift 1 @ 3\mod_1234172889468_21.doc x @ 27460 @ 1 @ 17 Connect DevicesPos : 76 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Leiter an C AGE C LAM P ans chli eßen ( allgemei n) - Übersc hrift 2 und Text @ 3\mod_1225448660171_21.doc x @ 24928 @ 2 @ 17.1 Connecting a Conductor to the CAGE CLAMP ®The WAGO CAGE CLAMP ® connection is appropriate for solid, stranded andfinely stranded conductors.Only connect one conductor to each CAGE CLAMP® !Only one conductor may be connected to each CAGE CLAMP ®.Do not connect more than one conductor at one single connection!If more than one conductor must be routed to one connection, these must beconnected in an up-circuit wiring assembly, for example using WAGO feed-through terminals.Exception:If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule tojoin the wires together. The following ferrules can be used:Length: 8 mmNominal cross section max. : 1 mm 2 for 2 conductors with 0.5 mm 2 eachWAGO product: 216-103 or products with comparable properties1. For opening the CAGE CLAMP ® insert the actuating tool into the openingabove the connection.2. Insert the conductor into the corresponding connection opening.3. For closing the CAGE CLAMP ® simply remove the tool. The conductor isnow clamped firmly in place.Figure 11: Connecting a Conductor to a CAGE CLAMP ®Pos : 77 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1