Operation G 5042 wc_tx001049gb.fm4.12 Main Line Circuit BreakerSee Graphic: wc_gr005866The main line circuit breaker (a) is located on the control panel.In the off “O” position, this breaker interrupts power from the selectorswitch to the terminal lugs at the bottom of the generator panel.NOTICE: Before shutting down the generator or performing anyservice to the generator unit, make sure the main circuit breaker is inthe off “O” position.The convenience receptacles are not connected through the main linecircuit breaker but are connected directly to the generator windings. Asa result, the receptacles are powered even with the main breaker in theoff “O” position. To turn off power to receptacles, open the individualcircuit breakers provided for each.NOTE: The warning light (d) will flash and the message MAINBREAKER OPEN will display on the LCD panel when the main linecircuit breaker is in the off “O” position and the controller has power.ELECTROCUTION HAZARD! High voltage is present inside thispanel when the generator is operating!WARNINGAØ HZVRBaslerDIAGNOSTICSDIAGNOSENDIAGNOSTICOSDIAGNOSTICSAUSAUSAPAGADOAPAGADOARRETARRETOFFOFFREMOTE STARTREMOTE STARTFERNSTARTFERNSTARTARRANQUE REMOTOARRANQUE REMOTODEMARRAGE ADEMARRAGE ADISTANCEDISTANCESTART / LAUFENSTART / LAUFENARRANQUE / MARCHAARRANQUE / MARCHADEMARRER / MARCHEDEMARRER / MARCHESTART / RUNSTART / RUNwc_gr005866wc_gr005866g