6 Related Drive ParametersYASKAWA ELECTRIC TOBP C730600 89D YASKAWA AC Drive Option SI-EP3 Installation Manual 39H5-11(043C)Communications ENTERFunction SelectionSelects whether an Enter command is necessary tochange parameter values via MEMOBUS/Modbuscommunications.0: Parameter changes are activated when ENTERcommand is written1: Parameter changes are activated immediatelywithout use of ENTERcommandDefault: 0 <14>Range: 0, 1<1> Set b1-02 = 3 to start and stop the drive with the PROFINET master device using serial communications.Set b1-01 = 3 to control the frequency reference of the drive via the master device.<2> Setting this parameter to 3 or 4 will cause the drive to continue operation after detecting a fault. Take propermeasures such as installing an emergency stop switch when using settings 3 or 4.<3> Refer to the drive manual to know if settings 4 and 5 are available. Settings 4 and 5 are available in A1000software versions PRG: 1021 and later.<4> The setting range for 1000-Series drives is different for different software versions. Refer to the instructionmanual of a specific drive for more information.<5> Control method availability of this parameter depends on product series. 1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.In AOLV/PM, this value is read as the Torque Limit. GA500 Drive: Parameter is available in OLV, AOLV/PM, and EZOLV.This value is read as the Torque Limit. GA700, GA800 Drives: Parameter is available in OLV, CLV, AOLV, AOLV/PM, CLV/PM, and EZOLV.In OLV and EZOLV, this value is read as the Torque Limit.<6> The setting specifies that network communications provide the torque reference or torque limit. The motor maynot rotate if the PLC does not supply a torque reference or torque limit.<7> Default setting is 1 for GA500.<8> Not available on 1000-series drives.<9> Cycle power for setting changes to take effect. Set F6-15 to 1 (Enable), to have settings take effect immediately onnon-1000 series drives.<10> Set F7-01 to F7-04 when F7-13 is set to 0. All IP Addresses (F7-01 to F7-04) must be unique.<11> Set F7-01 to F7-12 when F7-13 is set to 0.<12> Set F7-15 when F7-14 is not set to 1.<13> If a value other than 0 is assigned to parameters F7-23 to F7-27 and F7-33 to F7-37 by the drive, that value willtake precedent over a value set by the configuration software. If the value in the drive is 0 (default), the value fromthe configuration software is used.<14> The default setting is different for different product series. Refer to the instruction manual of a specific drive formore information.No.(Hex.) Name Description Values