32 YASKAWA ELECTRIC TOBP C730600 84D YASKAWA AC Drive Option SI-N3 Installation Manual6 Related Parameters6 Related ParametersThe parameters in Table 7 set the drive for operation with the option. Confirm proper settingof all parameters in Table 7 before starting network communications. Refer to the manualpackaged with the drive for details on setting parameters.Note: Hex.: MEMOBUS addresses that you can use to change parameters over networkcommunication are represented in hexadecimal numbers.Table 7 Related ParametersNo.(Hex.) Name Description Valuesb1-01(0180)<1>Reference 1 SourceSelects the input method for frequency reference.0: Keypad1: Analog Input2: Memobus/Modbus Communications3: Option PCB4: Pulse Train InputDefault: 1Range: 0 to 4b1-02(0181)<1>Run Command 1 SourceSelects the input method for the Run command.0: Keypad1: Digital Input2: Memobus/Modbus Communications3: Option PCBDefault: 1Range: 0 to 3d5-01(029A)Torque ControlSelection0: Speed Control1: Torque ControlDefault: 0Range: 0, 1F6-01(03A2)Communications ErrorSelectionSelects drive response when a bUS error is detected duringcommunications with the option.0: Ramp to Stop1: Coast to Stop2: Fast Stop (Use C1-09)3: Alarm Only <2>4: Alarm-Run at d1-04 <2> <3>5: Alarm-Ramp to Stop <3>Default: 1Range: 0 to 5 <4>F6-02(03A3)Comm External Fault(EF0) DetectSelects the condition for external fault detection (EF0).0: Always detected1: Detection during run onlyDefault: 0Range: 0, 1F6-03(03A4)Comm External Fault(EF0) SelectSelects drive response for external fault input (EF0)detection during option communications.0: Ramp to Stop1: Coast to Stop2: Fast Stop (Use C1-09)3: Alarm Only <2>Default: 1Range: 0 to 3F6-06(03A7)<5>Torque Reference/Limitby CommEnabling this parameter allows d5-01 to determine whetherthe value is read as the Torque Limit value (d5-01 = 0) orthe Torque Reference value (d5-01 = 1).0: Disabled1: Enabled <6>Default: 0Range: 0, 1