6 Related ParametersYASKAWA ELECTRIC TOBP C730600 84D YASKAWA AC Drive Option SI-N3 Installation Manual 35F6-70(03C7)<12>Dynamic In Assembly159 Param 3 (DIA159 3)The data in configurable input 3 is read from theMEMOBUS/Modbus address defined by this parameter.Default: 0x0000Min: 0x0000Max: 0xFFFFF6-71(03C8)<12>Dynamic In Assembly159 Param 4 (DIA159 4)The data in configurable input 4 is read from theMEMOBUS/Modbus address defined by this parameter.Default: 0x0000Min: 0x0000Max: 0xFFFFU6-97(07F7) OPT SPARE 4 Displays option software version –U6-98(07F8) First FaultDisplays previous faulted status.0: No fault1: Option failure2: PLC in idle state3: Force fault1000: Network power loss1001: Connection timeout1002: Duplicate MAC ID1003: Bus-offNote: Used in option faults–U6-99(07F9) Current FaultDisplays the most recent fault status.0:No fault1: Option failure2: PLC in idle state3: Force fault1000: Network power loss1001: Connection timeout1002: Duplicate MAC ID1003: Bus-offNote: Used in option faults–<1> To start and stop the drive with the DeviceNet master device using serial communications, set b1-02 to 3 or set theNet Control bit in the assemblies or Control Supervisor Object. To control the frequency reference of the drive viathe master device, set b1-01 to 3 or set the Net Reference bit in the assemblies or AC/DC object.<2> Setting this parameter to 3 or 4 will cause the drive to continue operation after detecting a fault. Take propermeasures such as installing an emergency stop switch when using settings 3 or 4.<3> Refer to the drive manual to know if settings 4 and 5 are available. Settings 4 and 5 are available in A1000software versions PRG: 1021 and later.<4> The setting range for 1000-Series drives is different for different software versions. Refer to the instruction manualof a specific drive for more information.<5> Control method availability of this parameter depends on product series. 1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.In AOLV/PM, this value is read as the Torque Limit. GA700, GA800 Drives: Parameter is available in OLV, CLV, AOLV, AOLV/PM, CLV/PM, and EZOLV.In OLV and EZOLV, this value is read as the Torque Limit.<6> The setting specifies that network communications provide the torque reference or torque limit. The motor maynot rotate if the PLC does not supply a torque reference or torque limit.<7> Supported on PRG: 1115 and later and only on GA700, GA800 drives. Not available on 1000-series drives.<8> All MAC addresses must be unique.<9> Cycle power for setting changes to take effect.<10> The default setting depends on region code. Refer to Table 8 on page 36 for more information.No.(Hex.) Name Description Values