1 from 16 at 60Hz interference frequency6.4.5 Analog part - Parameterization13Byte of parameter data are available for the configuration. Parameters of the analogpart may be set by means of the AI5/AO2 submodule of the Siemens CPU during hard-ware configuration.By using the record set 1 of the SFC 55 "WR_PARM" you may alter the parameterizationin the module during runtime. The time needed until the new parameterization is valid canlast up to 2ms. During this time, the measuring value output is 7FFFFh.The following table shows the structure of the parameter data:Byte Bit 7 ... Bit 0 Default0 Temperature unitn Bit 2, 0: reservedn Bit 4, 3: Unit00b = Celsius01b = Fahrenheit10b = Kelvinn Bit 7...5: reserved00h1 Integration time, Interference frequency suppression00b = 2.5ms, 400Hz *01b = 16.6ms, 60Hz10b = 20.0ms, 50Hzn Bit 1, 0: Analog Input Channel 0n Bit 3, 2: Analog Input Channel 1n Bit 5, 4: Analog Input Channel 2n Bit 7, 6: Analog Input Channel 3AAh2 reserved3 Measurement Analog Input Channel 0n Bit 3 ... 0: Measuring rangen Bit 7 ... 4: Measuring typeMeasurement range:0h: deactivated2h:Current 0...20mA3h: Current 4...20mA4h: Current +/-20mA19h4 Measurement Analog Input Channel 1n Bit 3 ... 0: Measuring rangen Bit 7 ... 4: Measuring type19h*) Here the VIPA CPU uses internally the value 1.25ms respectively 800Hz.Parameter dataRecord set 1VIPA System 300S+Deployment I/O peripheryAnalog part > Analog part - ParameterizationHB140 | CPU-SC | 313-5BF23 | en | 19-01100