Here it should apply:n if value1 = value2 activate output Q 124.0n if value1 > value2 activate output Q 124.1n if value1 < value2 activate output Q 124.2n You have administrator rights for your PC.n WinPLC7 is installed and activated as "Profi" version.n One SPEED7 CPU and one digital output module are installed and cabled.n The Ethernet PG/OP channel of the CPU is connected to your Ethernet network. YourCPU may be connected to your PC with an Ethernet cable either directly or via hub/switch.n WinPCap for station search via Ethernet is installed.n The power supply of the CPU and the I/O periphery are activated and the CPU is inSTOP state.8.3.2 Project engineering1. Start WinPLC7 ("Profi" version)2. Create and open a new project with [Create a new solution].1. For the call of the hardware configurator it is necessary to set WinPLC7 from theSimulator-Mode to the Offline-Mode. For this and the communication via Ethernetset "Target: TCP/IP Direct".2. Double click to ‘Hardware stations’ and here at ‘Create new’ .3. Enter a station name. Please consider that the name does not contain any spaces.4. After the load animation choose in the register Select PLC-System the system"VIPA SPEED7" and click to [Create]. A new station is created.5. Save the empty station with [Strg]+[S].6. By double click or drag&drop the according VIPA CPU in the hardware catalog at‘CPU SPEED7’ the CPU is inserted to your configuration.7. For output place a digital output module, assign the start address 124 and save thehardware configuration.PreconditionHardware configurationVIPA System 300S+ WinPLC7Example project engineering > Project engineeringHB140 | CPU-SC | 313-5BF23 | en | 19-01 171