9JOHNSON CONTROLSFORM 100.50-SU3 (1207)“CV OCCUPIED COOLING SETPOINT” – Must beset using Parameter 10 under the PROGRAM key onthe Simplicity control board or under the COOLINGSETUP tab in the Simplicity PC software package.Settable between 45.0º F and 99.0º F. The default valueis 72.0º F.“CV UNOCCUPIED COOLING SETPOINT” – Mustbe set using Parameter 12 under the PROGRAM keyon the Simplicity control board or under the COOLINGSETUP tab in the Simplicity PC software package.Settable between 45.0º F and 99.0º F. The default valueis 85.0º F.HARDWIRED OR COMMUNICATED SPACE SENSORCONTROL – HEATINGField WiringConnect the space sensor wiring to the field wiring screwconnections on the Unit Controller (see Appendix 1).Misc. ConnectionsNo additional connections required.Programming“HEATING MODE OPERATION ENABLED” – Mustbe set to ON using Parameter 54 under the PROGRAMkey on the Simplicity control board or under theHEATING SETUP tab in the Simplicity PC softwarepackage.“CV OCCUPIED HEATING SETPOINT” – Must beset using Parameter 11 under the PROGRAM key onthe Simplicity control board or under the HEATINGSETUP tab in the Simplicity PC software package.Settable between 45.0º F and 99.0º F. The default valueis 68.0º F.“CV UNOCCUPIED HEATING SETPOINT” – Mustbe set using Parameter 13 under the PROGRAM keyon the Simplicity control board or under the COOLINGSETUP tab in the Simplicity PC software package.Settable between 45.0º F and 99.0º F. The default valueis 60.0º F.“STAGES OF HEATING AVAILABLE” - Must be setusing Parameter 81 under the PROGRAM key on theSimplicity control board or under the HEATING SETUPtab in the Simplicity PC software package.STAND ALONE CONTROL – COOLINGField WiringNo additional connections required.Misc. ConnectionsNo additional connections required.Programming“COOLING MODE OPERATION ENABLED” – Mustbe set to ON using Parameter 53 under the PROGRAMkey on the Simplicity control board or under theCOOLING SETUP tab in the Simplicity PC softwarepackage.“CV OCCUPIED COOLING SETPOINT” – Must beset using Parameter 10 under the PROGRAM key onthe Simplicity control board or under the COOLINGSETUP tab in the Simplicity PC software package.Settable between 45.0º F and 99.0º F. The default valueis 72.0º F.“CV UNOCCUPIED COOLING SETPOINT” – Mustbe set using Parameter 12 under the PROGRAM keyon the Simplicity control board or under the COOLINGSETUP tab in the Simplicity PC software package.Settable between 45.0º F and 99.0º F. The default valueis 85.0º F.