036-21121-002 Rev. A (0602)Unitary Products Group 9Multipliers for determining the performance with other indoor sections.COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. H1RA018S06INDOOR COIL MODEL NO. G1FA024S14,17CONDENSERENTERING AIRTEMPERATUREID CFM 550 650 750ID DB (∞F) 85 80 70 85 80 70 85 80 70ID WB (∞F) 72 67 57 72 67 57 72 67 5775T.C. 20.6 19.7 18.1 20.7 19.8 18.5 20.8 19.8 18.9S.C. 12.7 12.8 12.3 13.3 13.5 13.4 13.7 13.8 14.0K.W 1.68 1.65 1.64 1.72 1.71 1.70 1.75 1.74 1.7385T.C. 20.6 19.3 17.4 20.9 19.6 18.0 21.1 19.8 18.4S.C. 12.7 12.6 11.9 13.5 13.4 13.1 14.1 14.0 13.8K.W 1.58 1.54 1.53 1.62 1.59 1.58 1.65 1.63 1.6295T.C. 19.0 17.5 15.5 19.5 18.0 16.1 19.8 18.2 16.5S.C. 12.8 12.4 11.5 13.7 13.3 12.8 14.5 14.1 13.6K.W 1.97 1.91 1.90 2.02 1.96 1.95 2.05 2.00 1.99105T.C. 18.4 16.6 14.2 18.9 17.1 15.0 19.2 17.4 15.4S.C. 12.5 11.8 10.7 13.6 12.8 12.0 14.4 13.7 12.8K.W 1.82 1.77 1.75 1.88 1.82 1.80 1.91 1.86 1.83115T.C. 16.3 14.5 11.9 16.9 15.0 12.7 17.2 15.2 13.1S.C. 12.3 11.2 10.0 13.5 12.4 11.2 14.3 13.2 12.0K.W 2.24 2.19 2.14 2.31 2.24 2.19 2.35 2.28 2.22125T.C. 14.3 12.3 9.7 14.9 13.0 10.5 15.2 13.1 10.8S.C. 12.0 10.6 9.3 13.3 11.9 10.4 14.2 12.8 11.2K.W 2.66 2.61 2.53 2.74 2.66 2.58 2.79 2.70 2.61NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFMAir Handler Coil T.C. S.C. KWN1AHB0806 G2FD024S17 1.06 1.06 0.99F2RC/F2FC024 0.97 0.97 0.99G1FA030S14 1.06 1.06 0.99G1HD024 1.03 1.03 0.95G1NA024S17G 1.00 0.94 0.98G1UA024S14,17 1.00 1.00 1.00G1UA030S14 1.06 1.06 0.99G2FD024S14,17 1.06 1.06 0.99G2FD030S17 1.08 1.08 1.00G2FD035S14 1.08 1.08 1.00