362242-YIM-B-010930 Johnson Controls Unitary ProductsTABLE 16: SUPPLY AIR BLOWER PERFORMANCE (BP036 BELT DRIVE) - SIDE DUCT APPLICATIONAirFlow(CFM)Available External Static Pressure - IWG 11. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied Drive Standard Drive Option HIgh Static Drive Option800 633 0.37 734 0.41 828 0.47 914 0.54 994 0.61 1069 0.69 1139 0.77 1205 0.85 1268 0.94 1328 1.031000 656 0.41 757 0.46 851 0.52 937 0.58 1017 0.66 1092 0.73 1162 0.81 1228 0.90 1291 0.99 1351 1.081200 680 0.47 781 0.52 874 0.58 960 0.65 1041 0.72 1115 0.80 1185 0.88 1251 0.96 1314 1.05 1375 1.141400 706 0.56 807 0.61 901 0.67 987 0.73 1067 0.80 1142 0.88 1212 0.96 1278 1.05 1341 1.13 1401 1.221600 737 0.67 839 0.72 932 0.77 1018 0.84 1098 0.91 1173 0.99 1243 1.07 1309 1.15 1372 1.24 1433 1.33FS 4TABLE 17: SUPPLY AIR BLOWER PERFORMANCE (BP036 BELT DRIVE) - BOTTOM DUCT APPLICATIONAirFlow(CFM)Available External Static Pressure - IWG 11. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.4. Field Supplied Drive.0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied Drive Standard Drive Option HIgh Static Drive Option800 612 0.38 722 0.43 824 0.48 918 0.55 1006 0.61 1087 0.69 1163 0.77 1235 0.85 1304 0.94 1370 1.021000 638 0.42 748 0.47 849 0.53 944 0.59 1031 0.66 1112 0.74 1188 0.82 1260 0.90 1329 0.98 1395 1.071200 663 0.48 773 0.53 875 0.59 969 0.65 1056 0.72 1138 0.80 1214 0.88 1286 0.96 1354 1.04 1420 1.131400 692 0.57 802 0.61 904 0.67 998 0.73 1085 0.80 1167 0.88 1243 0.96 1315 1.04 1383 1.13 1449 1.211600 726 0.67 836 0.72 938 0.78 1032 0.84 1119 0.91 1201 0.98 1277 1.06 1349 1.15 1417 1.23 1483 1.32FS 4TABLE 18: SUPPLY AIR BLOWER PERFORMANCE (BP048 BELT DRIVE) - SIDE DUCT APPLICATIONAirFlow(CFM)Available External Static Pressure - IWG 11. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.3. kW = BHP x 0.932.0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPField Supplied Drive Standard Drive Option HIgh Static Drive Option1000 699 0.42 782 0.49 862 0.56 939 0.64 1012 0.73 1083 0.82 1151 0.91 1217 1.01 1280 1.11 1341 1.211200 727 0.45 810 0.52 889 0.60 966 0.68 1040 0.76 1110 0.85 1179 0.95 1244 1.04 1308 1.14 1369 1.241400 759 0.51 842 0.58 922 0.65 998 0.73 1072 0.82 1143 0.91 1211 1.00 1276 1.10 1340 1.20 1401 1.301600 795 0.60 878 0.67 958 0.74 1035 0.82 1108 0.91 1179 1.00 1247 1.09 1313 1.19 1376 1.28 1438 1.391800 836 0.72 919 0.79 999 0.87 1075 0.95 1149 1.03 1220 1.12 1288 1.22 1353 1.31 1417 1.41 1478 1.512000 880 0.89 963 0.96 1042 1.04 1119 1.12 1193 1.20 1263 1.29 1331 1.39 1397 1.48 1460 1.58 1522 1.68