362242-YIM-B-01096 Johnson Controls Unitary ProductsINSTALLATIONINSTALLATION SAFETY INFORMATIONRead these instructions before continuing this appli-ance installation. This is an outdoor combination heat-ing and cooling unit. The installer must assure thatthese instructions are made available to the consumerand with instructions to retain them for future reference.1. Install this unit only in a location and position asspecified on page 7 of these instructions.2. This equipment is not to be used for temporaryheating of buildings or structures under construc-tion.LIMITATIONSThese units must be installed in accordance with thefollowing national and local safety codes:In U.S.A.:• National Electrical Code ANSI/NFPA No. 70.In Canada:• Current Canadian Electrical Code C22.1.• Local plumbing and waste water codes.• Other applicable local codes.Refer to the Unit Application Data Table 1 and theElectrical Data table for the unit.If components are to be added to a unit to meet localcodes, they are to be installed at the dealer's and/orthe customer's expense.Size of unit for proposed installation should be basedon heat loss/heat gain calculation made according tothe methods of the Air Conditioning Contractors ofAmerica (ACCA).This unit is not to be used for temporary heating ofbuildings or structures under construction.The Simplicity® control board used in thisproduct will effectively operate the coolingsystem down to 0°F when this product isapplied in a comfort cooling application forpeople. An economizer is typically included inthis type of application. When applying thisproduct for process cooling applications(computer rooms, switchgear, etc.), pleasereference applications bulletin AE-011-07 orcall the applications department for UnitaryProducts @ 1-877-UPG-SERV for guidance.Additional accessories may be needed forstable operation at temperatures below 30°F.TABLE 1: UNIT APPLICATION DATA (BP)UNIT MODEL NUMBER 036 048 060 072Voltage Variation,Min. / Max.11. Utilization range “A” in accordance with ARI Standard 110.208/230 187/253460 414/506575 518/630Supply Air CFM, Nom. 1200 1600 2000 2400Wet Bulb Temperature (ºF) of Air onEvaporator Coil, Min./Max 57/72Dry Bulb Temperature (ºF) of Air onCondenser Coil, Min./Max. 0/125