UMG 96-PA www.janitza.de165. Installation5. 1 Installation siteThe device is suitable for installation innon-mobile and weather-protected controlpanels in indoor environments.Plan on an earth for conducting control pan-els.5. 2 Installation positionThe cut-out dimensions of the control panelare 92+0,8 mm x 92+0,8 mm.To achieve sufficient ventilation, take thefollowing measures:• Install the device vertically.• Maintain a minimum clearance of 50 mmabove and below.• Maintain a minimum clearance of 20 mmon each side.Fig. Back view of the installation posi-tion of the UMG 96-PAmCAUTION!Material damage mayresult if the installation in-structions are not followed!Not following the installation instructionsmay damage or destroy your device.Comply with the details on the installationposition in sections „Installation“ and„Technical Data“.5. 3 Securing the deviceThe device is secured in the control panelwith the side mounting brackets. The brack-ets are to be removed e.g. using a screw-driver as a horizontal level before the deviceis put in.Fig. Side view of UMG 96-PA with mounting brackets.The brackets can be loosened by leveraging them hori-zontally with a screwdriver.Assembly plateClamping screwScrewdriverMountingbracketsOnce the clamping screwstouch the surface of theassembly plate: use two furtherrotations at most to securethe deviceThen slide in and snap the brackets intoplace, and finally screw in the screws to se-cure the device.• Turn the clamping screws until they justtouch the assembly plate.• Then tighten the clamping screws with twomore rotations each (the mounting brack-ets may be destroyed if the screws aretightened too much).