14 Start-up, control with I/O and ID runHow to start up the drive How to start up the drive using the First start assistant on theassistant control panelSafetyDo not start-up the drive unless you are a qualified electrician.Read and obey the instructions in chapter Safety instructions at the beginning of theHardware manual of the drive. Ignoring the instructions can cause physical injury or death, ordamage to the equipmentCheck the installation. See chapter Installation checklist in the Hardware manual of thedrive.Make sure there is no active start on (DI1 in factory settings, that is, ABB standardmacro). The drive will start up automatically at power-up if the external runcommand is on and the drive is in the remote control mode.Check that the starting of the motor does not cause any danger.De-couple the driven machine if• there is a risk of damage in case of an incorrect direction of rotation, or• a Normal ID run is required during the drive start-up, when the load torque is higherthan 20% or the machinery is not able to withstand the nominal torque transient duringthe ID run.Hints on using the assistant control panelThe two commands at the bottom of the display(Options and Menu in the figure on the right),show the functions of the two softkeys andlocated below the display. The commandsassigned to the softkeys vary depending on thecontext.Use keys , , and to move the cursorand/or change values depending on the activeview.Key shows a context-sensitive help page.For more information, see ACS-AP-x assistantcontrol panels user’s manual (3AUA0000085685[English]).1 – First start assistant guided settings:Language, date and time, and motor nominal valuesHave the motor name plate data at hand.Power up the drive.?