Fieldbus control through the embedded fieldbus interface (EFB) 409 Control Word for the DCU ProfileThe embedded fieldbus interface writes the fieldbus Control Word as is to the driveControl Word bits 0 to 15. Bits 16 to 32 of the drive Control Word are not in use.8 JOGGING_1 1 Request running at Jogging 1 speed.Note: This bit is effective only if the fieldbus interface isset as the source for this signal by drive parameters.0 Continue normal operation.9 JOGGING_2 1 Request running at Jogging 2 speed.Note: This bit is effective only if the fieldbus interface isset as the source for this signal by drive parameters.0 Continue normal operation.10 REMOTE_CMD1 Fieldbus control d.0 Control Word <> 0 or Reference <> 0: Retain last ControlWord and Reference.Control Word = 0 and Reference = 0: Fieldbus control d.Reference and deceleration/acceleration ramp arelocked.11 EXT_CTRL_LOC1 Select External Control Location EXT2. Effective if thecontrol location is parameterized to be selected from thefieldbus.0 Select External Control Location EXT1. Effective if thecontrol location is parameterized to be selected from thefieldbus.12 USER_0 Writable control bits that can be combined with drive logicfor application-specific functionality.13 USER_114 USER_215 USER_3Bit Name Value State/Description0 STOP 1 Stop according to the Stop Mode parameter or the stopmode request bits (bits 7…9).0 (no op)1 START 1 Start the drive.0 (no op)Bit Name Value STATE/Description