254 ParametersExternal 24V The drive control unit is powered from an external powersupply.195.03 Temp inu ambient Defines the maximum ambient temperature. This temperatureis used to calculate the estimated drive temperature. If themeasured drive temperature exceeds this estimated value,an alarm (COOLING) or fault (COOLING) is generated.0 … 55 °C Drive ambient temperature. 1 = 1 °C9797 User motor par Motor values supplied by the user that are used in the motormodel.97.01 Use given params Activates the motor model parameters 97.02…97.14 and therotor angle offset parameter 97.20.Notes:• Parameter value is automatically set to zero when ID run isselected by parameter 99.13 IDrun mode. The values ofparameters 97.02…97.20 are updated according to themotor characteristics identified during the ID run.• This parameter cannot be changed while the drive isrunning.NoUserPars Parameters 97.02…97.20 inactive. 0UserMotPars The values of parameters 97.02…97.14 are used in the motormodel.1UserPosOffs The value of parameter 97.20 is used as the rotor angleoffset. Parameters 97.02…97.14 are inactive.2AllUserPars The values of parameters 97.02…97.14 are used in the motormodel, and the value of parameter 97.20 is used as the rotorangle offset.397.02 Rs user Defines the stator resistance RS of the motor model.0.00000 … 0.50000p.u.Stator resistance in per unit. 100000 =1 p.u.97.03 Rr user Defines the rotor resistance RR of the motor model.Note: This parameter is valid only for asynchronous motors.0.00000 … 0.50000p.u.Rotor resistance in per unit. 100000 =1 p.u.97.04 Lm user Defines the main inductance LM of the motor model.Note: This parameter is valid only for asynchronous motors.0.00000 …10.00000 p.u.Main inductance in per unit. 100000 =1 p.u.97.05 SigmaL user Defines the leakage inductance σLS.Note: This parameter is valid only for asynchronous motors.0.00000 … 1.00000p.u.Leakage inductance in per unit. 100000 =1 p.u.97.06 Ld user Defines the direct axis (synchronous) inductance.Note: This parameter is valid only for permanent magnetmotors.0.00000 …10.00000 p.uDirect axis inductance in per unit. 100000 =1 p.u.97.07 Lq user Defines the quadrature axis (synchronous) inductance.Note: This parameter is valid only for permanent magnetmotors.No. Name/Value Description FbEq