Electrical installation 85Connecting the motor cables (units with du/dt andcommon motor terminal)If the drive is equipped with du/dt and common motor terminal, the motor cables connectto a common motor terminal.Connection diagramCommon guideline for connecting the motor cablesWARNING! Obey the instructions in chapter Safety instructions. If youignore them, injury or death, or damage to the equipment can occur.1. Do the steps in section Precautions before electrical work before you start the work.2. Open the door of the common motor terminal or sine filter cubicle and remove theshrouding.3. Lead the cables into the cubicle. Make the 360° earthing arrangement at the cableentry as shown.4. Cut the cables to suitable length. Strip the cables and conductors.5. Twist the cable screens into bundles and connect the bundles to the PE busbar in thecubicle.U2V2W2PEThe recommended cable types are given in chapter Guidelines for planning the electrical installation.M3~U1W1V1PEModule cubicle(s) du/dt and common motorterminalGrommet (IP54 units only)