DescriptionValue or Value range/ DefaultNameData type: IntegerAccess: No limitationsStatus of the integrated SNTP servers timesynchronization routine. Value is 0 whennot in use and 1 when in use. By writing0 the client is started and by writing 1 it isstopped.0 = Not in use1 = In useDefault: 1In useStatus of the integrated SNTP servers timesynchronization routine. Value is falsewhen operation fails and true when oper-ating OK.False = FailureTrue = OKTimesync statusIEC 61850 subnetwork attributes3.3.3.Table 3.3.3-1 IEC 61850 subnetwork attributesDescriptionValue or Value range/ DefaultNameData type: IntegerAccess: No limitationsThe state of the subnetwork whether it isin use or not. When a subnetwork is notin use, no data can be transmitted on it,and no data is received from it. When asubnetwork is stopped by setting the inuse attribute to 0, all data transmission onthe subnetwork ceases and all open con-nections to the devices will be closed.Single devices in use attribute may be setto 1 and this operation also takes thesubnetwork in use. Now only the onedevice is in use. If the subnetwork in useis set to 1, the rest of the devices are takenin use. The in use attribute has no affecton devices in simulation mode.0 = Not in use, the subnetworkcommunication is stopped1 = In useDefault: 1In useData type: IntegerAccess: Read-onlyIndicates the operating status of the device89 = Initialize error90 = Not connected91 = Initializing100 = Ready101 = Suspended (=Not in use)102 = SimulatedObject status63COM600 series 5.01MRS758690Master Protocols (Ethernet) and Applications Technical Refer-ence Manual