PROFIdrive parameters128I&M (Identification & Maintenance) recordsI&M records can be read e.g. with the DTM tool. The FPBA-01supports the mandatory I&M0 record as well as the optional I&M1and I&M2 records.Call-REQ-PDU telegram for read/write access to I&M records:Response structure for I&M0 (Read-only)Contents Size Coding NotesDP-V1headerFunction_Num 1 Octet 5Fh fixedSlot_Number 1 Octet 0Ö255 variableIndex 1 Octet 255 fixedLength 1 Octet 4 / 68 Call Header only / WriteCallHeaderExtended_Function_Num 1 Octet 08h Indicates ìCallî, fixedreserved 1 Octet 00h fixedFI_Index 2 Octets 65000Ö Subindex of I&M0 Record65000 = I&M065001 = I&M165002 = I&M2IM_Function 64 Octets Data Write only (I&M1 or I&M2)Contents Size CodingHeader Manufacturer-specific 10 Octets ìFPBA-01îI&MblockMANUFACTURER_ID 2 Octets 0x1A = ABB AutomationORDER_ID 20 Octets ì68469325î (for FPBA-01 kit)SERIAL_NUMBER 16 Octets Serial number of FPBA moduleHARDWARE_REVISION 2 Octets Hardware version of FPBA moduleSOFTWARE_REVISION 4 Octets Format: V255.255.255E.g. V1.0.0 = software version 100AREVISION_COUNTER 2 Octets (marks a change of hardware or itsparameters)PROFILE_ID 2 Octets 3A00 (Ö3AFF) PROFIdrivePROFILE_SPECIFIC_TYPE 2 Octets 0 = no specific typeIM_VERSION 2 Octets 0x0101 = version 1.1IM_SUPPORTED 2 Octets 3 = I&M0, I&M1 and I&M2 supported