Section 13 Testing functionality by secondary injection13.1 Testing disturbance report13.1.1 Introduction M17101-2 v6The following sub-functions are included in the disturbance report function:• Disturbance recorder• Event list• Event recorder• Trip value recorder• IndicationsIf the disturbance report is enabled, then its sub-functions are also set up and so it isnot possible to only disable these sub-functions. The disturbance report function isdisabled (parameter Operation = Disabled) in PCM600 or the local HMI under Mainmenu/Settings/IED Settings/Monitoring/Disturbance report/DRPRDRE:1.13.1.2 Disturbance report settings M11746-2 v6When the IED is in test mode, the disturbance report can be made active or inactive. Ifthe disturbance recorder is turned on during test mode, recordings will be made. Whentest mode is switched off all recordings made during the test session are cleared.Setting OpModeTest for the control of the disturbance recorder during test mode arelocated on the local HMI under Main menu/Settings/IED Settings/Monitoring/Disturbance report/DRPRDRE:1.13.1.3 Disturbance recorder (DR) M11750-2 v6A Manual Trig can be started at any time. This results in a recording of the actualvalues from all recorded channels.The Manual Trig can be started in two ways:1. From the local HMI under Main menu/Disturbance records.1.1. Enter on the row at the bottom of the HMI called Manual trig.1MRK 502 073-UUS A Section 13Testing functionality by secondary injectionGenerator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 139Commissioning manual