13.11.1.4 Completing the test SEMOD54375-203 v6Continue to test another function or end the test by changing the TESTMODE setting toDisabled. Restore connections and settings to their original values, if they werechanged for testing purposes.13.11.2 Integrator TIGAPC GUID-D18B2BCA-A79B-4B04-860C-BE2122FECEA7 v2The integrator function TIGAPC can be tested by connecting a binary signal to theinput of the function and applying pulses to the function. Normally the Integrator willbe tested when testing the function the integrator is connected to, such as reversepower, loss of excitation and pole slip. When the function is configured, test it togetherwith the function that operates it.13.11.2.1 Completing the test GUID-5CD0314D-7D02-477E-BC16-12C82534E72D v2Continue to test another function or end the test by changing the Test mode setting toDisabled. Restore connections and settings to their original values, if they werechanged for testing purposes.13.12 Monitoring SEMOD53581-1 v113.12.1 Gas medium supervision SSIMG GUID-0A83B4D5-51FF-43CB-8DC7-AFCEA2BC7B69 v2Prepare the IED for verification of settings as outlined in Section "Preparing the IED toverify settings" in this chapter.Values of logical signals for SSIMG protection are available on the local HMI underMain menu/Tests/Function status/Monitoring/InsulationGas(63)/SSIMG(63):x,where x = 1, 2,....21.The Signal Monitoring in PCM600 shows the same signals that are available on thelocal HMI.Check that the input logical signal BLOCK is logical zero and that on the local HMI,the logical signals PRESALM, PRESLO, TEMPALM, TEMPLO, ALARM and LOCKOUTare logical zero.Section 13 1MRK 502 073-UUS ATesting functionality by secondary injection272 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062Commissioning manual