IEC11000045-1-en.vsdFrequency found bythe function Voltage and current signalstaus and TRIP indicationFfunction status field. Errors andabnormalities are displayed in orderto simplify trouble shooting.GUID-84947C77-215F-4007-AAC0-9433B8444396 V1 EN-USFigure 10: ICT signals and function indication panel9. When the installing procedure is successful, select the Submit and save inreport button. ICT will now forward a more accurate frequency to Parametersetting. In the Parameter setting tool, write the newly acquired parameter to IED.The accurate setting of this frequency is essential for proper operation of theprotection under different operating conditions.6.4 Performing calibration GUID-DE96CE75-A268-4FE1-AD9D-093EA1F2ECBA v21. From the Calibrating tab, select the first sub tab, i.e. Step1: Measurement 1.2. Make sure you have not attached any additional impedance in parallel with therotor.3. From the ICT toolbar, select the Start reading from IED button.The generator shall be in a condition that is as close as possible to the normaloperating condition as during the Installation.It is very important that calibration steps 1 to 3 is performed in theproper order. If not, the calibration might fail. If readings are notstable during the step, a warning to repeat the step may besuggested; the step shall be repeated in order to avoid that thecalibration fails.4. When the statistical error of the performed continuous measurements reaches anacceptable value, the indicator bar reaches the stability region (turned green), andit is allowed to select the Submit button.Clicking the Submit button the result is stored for later calculations. ICTautomatically shifts to the second calibration sub tab, Step 2: Measurement 2.1MRK 502 073-UUS A Section 6Calibrating injection based sensitive rotor earth fault protectionGenerator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 67Commissioning manual