6.5 View monitoring values6.5.1 Service values CVMMXUMain menu/Measurement/Monitoring/ServiceValues(MMXU)/SVRDisplays up to three instances of CVMMXU with measured values for S, P, Q, PF, U,I, ILead, ILag and F.6.5.2 Current phasors CMMXUMain menu/Measurement/Monitoring/CurrentPhasors(MMXU)/CPAll three phase currents and their phase angles are displayed here.6.5.3 Voltage phasors VMMXU/VNMMXUMain menu/Measurements/Monitoring/VoltagePhasors(MMXU)/Phase - Phase/VPPhase to phase voltages and phase angles are displayed here.Main menu/Measurement/Monitoring/VoltagePhasors(MMXU)/PhaseEarth/VNPhase to ground voltages and phase angles are displayed here.6.5.4 Current sequence component CMSQIMain menu/Measurements/Monitoring/CurrentSequenceComponents(MSQI)/CSQThe current sequence component under monitoring displays the positive (I1), negative(I2) and zero sequence (I0) current values for a three phase line, both magnitude andphase angle for each component are displayed. These indicate how well balanced asystem is. In an ideal balanced system the zero sequence current should be zero, thepositive sequence current should be equal to the current of each phase with the samephase angle (relative to GPS) as the A phase signal and the negative sequence currentshould be zero.6.5.5 Voltage sequence component VMSQIMain menu/Measurements/Monitoring/VoltageSequenceComponents(MSQI)/VSQSection 6 1MRK506276-UUS BRead measured values32Operator's manual