9. Control displays the Synchronism-checkAutorecloser, and Apparatus controlfunctions. The Synchronism-checkand the Autorecloser functions include anumber of function related measurements such as calculated differences ofmeasurements and number and kind of reclosing attempts. Apparatus controlincludes up to 19 functions each with their own set of measurement data regardinginterlocking, breaker and isolator conditions.10. Scheme communication includes functions that display trip and other signals usedwhen interzone communication is deployed.11. Logic displays a choice of functions available to the operator. These are Trip logic,Event counter, Logic gate, Logic memory and Logic timer set each with their ownset of measurements.12. Monitoring displays a choice of functions available to the operator. Functionrelated measurements can be viewed by navigating to the screen for eachindividual function. One of the submenus shows the status of the LEDs on the HMI.13. Communication displays submenus for Remote communication and Stationcommunication including Receiving interlock information.All measurement descriptions in this document reflect the maximum number ofhardware units possible in any application. In reality the hardware in the IED will bechosen according to a particular application. For example, it is possible to equip a 1/1 x19” case IED with 14 I/O modules. In reality fewer I/O modules may be installed. Inthe measurements menu the operator will only see data from the hardware and softwareinstalled.11.2 IED test modeMain menu/Test/IED test modeDisplays a setting which is used to activate and deactivate functions so that tests can beperformed without endangering system stability and a setting with which events can beenabled or disabled.11.3 View binary input values11.3.1 OverviewBinary input values display the state of each individual input in the Binary inputmodules (BIM). These are indicated with a 1 or 0 depending on whether a signal ispresent or not. Binary input modules with enhanced pulse counting capabilities canreceive pulses used for power measurement. The number of pulses received is used tomeasure power.Section 11 1MRK506276-UUS BTest the IED70Operator's manual