AutoCont andtAutoContWait, Automatic continuation to the next shot ifthe CB is not closed within the set timeThe normal setting isAutoCont =Off. ThetAutoContWait is the length of time SMBRREC waitsto see if the breaker is closed whenAutoCont is set toOn. Normally, the setting can betAutoContWait = 2 sec.12.3 Apparatus control APC IP14560-1 v212.3.1 Application IP14931-1 v1M13443-4 v12The apparatus control is a function for control and supervising of circuit breakers,disconnectors, and earthing switches within a bay. Permission to operate is given afterevaluation of conditions from other functions such as interlocking, synchrocheck, operatorplace selection and external or internal blockings.The complete apparatus control function is not included in this product, andthe information below is included for understanding of the principle for the useof QCBAY, LOCREM, LOCREMCTRL, SCILO, SCSWI, SXCBR.Figure 116 gives an overview from what places the apparatus control function receivecommands. Commands to an apparatus can be initiated from the Control Centre (CC), thestation HMI or the local HMI on the IED front.Station HMIGWccStation busbreakers disconnectors earthing switchesIEC08000227.vsdApparatusControlIEDI/OLocalHMIApparatusControlIEDI/OApparatusControlIEDI/OLocalHMILocalHMIIEC08000227 V1 EN-USFigure 116: Overview of the apparatus control functionsFeatures in the apparatus control function:Section 12 1MRK 505 363-UEN AControl232Application manual