created from any available signal in the IED that is connected to the Event function (EVENT).The EVENT function block is used for LON and SPA communication.Analog and double indication values are also transferred through the EVENT function.15.5.3 Setting guidelines IP14841-1 v1M12811-3 v2The parameters for the Event (EVENT) function are set via the local HMI or PCM600.EventMask (Ch_1 - 16) M12811-5 v2The inputs can be set individually as:•NoEvents•OnSet, at pick-up of the signal•OnReset, at drop-out of the signal•OnChange, at both pick-up and drop-out of the signal•AutoDetectLONChannelMask orSPAChannelMask M12811-15 v2Definition of which part of the event function block that shall generate events:•Off•Channel 1-8•Channel 9-16•Channel 1-16MinRepIntVal (1 - 16) M12811-29 v3A time interval between cyclic events can be set individually for each input channel. This can beset between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cycliccommunication.M12811-34 v1It is important to set the time interval for cyclic events in an optimized way tominimize the load on the station bus.15.6 Disturbance report DRPRDRE IP14584-1 v215.6.1 IdentificationM16055-1 v7Function description IEC 61850 identification IEC 60617identificationANSI/IEEE C37.2device numberDisturbance report DRPRDRE - -Disturbance report A1RADR - A4RADR - -Disturbance report B1RBDR - B8RBDR - -1MRK 505 363-UEN A Section 15Monitoring297Application manual