6.2 View analog primary values6.2.1 OverviewThe analog primary values are analog quantities measured on the primary side ofthe TRM and reflect the actual current or voltage on the primary side of the CTs.The ratio is adjusted under settings and also depends on the rating of the TRM. 24primary values and phase angles are displayed in this view.6.3 View analog secondary values6.4 View analog mean values6.4.1 OverviewMeasurements from the Milliampere Input Module (MIM) are found in this part ofthe measurements menu. Data from either the hard wired mA module or SignalMatrix Tool mA modules are shown here.6.4.1.1 mA input module MIMMain menu/Measurements/Analog mean values/mA modules/MIM:xDisplays input data from the milli-ampere module which has six inputs. Each inputhas a range of +/- 20 mA. The value displayed on the screen is however dependanton the settings for the Milli-ampere Module. In the menu for settings, the range anda transformation factor can be adjusted to suit the application. This means that aninput 3 mA may be displayed as temperature of 45 degrees. The output valuesshown are without units.6.5 View monitoring values6.5.1 Service values CVMMXNMain menu/Measurement/Monitoring/ServiceValues(MMXN)/CVMMXN:xDisplays up to three instances of CVMMXN with measured values for S, P, Q, PF,U, I, ILead, ILag and F.Section 6 1MRK511251-UEN BRead measured values28Operator's manual