TZIDC DIGITAL POSITIONER | OI/TZIDC-EN REV. B 9IECEx Ex iEx markingMarking Ex ia IIC T6 or T4 GbEx ib IIC T6 or T4 GbType Examination Test Certificate IECEx TUN 04.0015XType Intrinsic safety ‘i’Standards IEC 60079-0:2011IEC 60079-11:2011Temperature DataTemperature class Ambient temperature TaTZIDC Ex ia IIC TZIDC Ex ib IICT4 Æ40 to 85 °C Æ40 to 85 °CT6* Æ40 to 40 °C* Æ40 to 40 °C* When using the ‘Limit monitor’ plugÆin module in temperature class T6, themaximum permissible ambient temperature range is Æ40 to 35 °C.Electrical DataIn ‘intrinsically safe Ex ib IIC / Ex ia IIC’ type of protection, onlyfor connection to a certified intrinsically safe circuit.Current circuit (terminal) Electrical information (maximum values)Signal circuit(+11 / Æ12)U i = 30 VI i = 320 mAPi = 1.1 WCi = 6.6 nFLi = negligibly smallContact input(+81 / Æ82)U i = 30 VI i = 320 mAPi = 1.1 WCi = 4.2 nFLi = negligibly smallSwitch output(+83 / Æ84)U i = 30 VI i = 320 mAPi = 500 mWCi = 4.2 nFLi = negligibly smallLocal communicationinterface (LCI)Only for connection to a programming device usingan ABB LCI adapter (Um á 30 V DC) outside thehazardous area.The following modules may be operated as an option:Current circuit (terminal) Electrical information (maximum values)Plug-in module for limitmonitor(+51 / Æ52)(+41 / Æ42)U i = 30 VI i = 320 mAPi = 250 mWCi = 3.7 nFLi = negligibly smallPlug-in module foranalog positionfeedback(+31 / Æ32)U i = 30 VI i = 320 mAPi = 1.1 WCi = 6.6 nFLi = negligibly smallSpecial conditions• For the ‘Limit monitor with proximity switches’ circuit,measures outside of the device must be implemented toprevent the rated voltage from being up-scaled by more than40 % due to transient disturbances.• It is only permissible to connect, disconnect, and switch livecircuits during installation or maintenance, or for thepurpose of carrying out repairs. Note: It is considered veryunlikely that a hazardous atmosphere would be present inZone 2 at the same time that installation, maintenance orrepair work was being carried out.• Only non-flammable gases may be used for pneumatic powersupply.• Only use suited cable entries that meet the requirements ofEN 60079-15.