ARCSARC1BLOCKREM_FLT_ARCOPR_MODEOPERATEARC_FLT_DETARCSARC2BLOCKREM_FLT_ARCOPR_MODEOPERATEARC_FLT_DETARCSARC3BLOCKREM_FLT_ARCOPR_MODEOPERATEARC_FLT_DETOR6B1B2B3B4B5B6OARCSARC1_OPERATEARCSARC1_OPERATEARCSARC2_OPERATEARCSARC2_OPERATEARCSARC3_OPERATEARCSARC3_OPERATEARCSARC1_ARC_FLT_DETARCSARC2_ARC_FLT_DETARCSARC3_ARC_FLT_DETARCSARC_OPERATEGUID-F3C5D80F-F26B-4B34-9C26-1F2F3FA0CA36 V1 ENTRPPTRC3BLOCKOPERATERST_LKOUTTRIPCL_LKOUTTRPPTRC4BLOCKOPERATERST_LKOUTTRIPCL_LKOUTTRPPTRC5BLOCKOPERATERST_LKOUTTRIPCL_LKOUTTRPPTRC3_TRIPTRPPTRC4_TRIPTRPPTRC5_TRIPARCSARC1_OPERATEARCSARC2_OPERATEARCSARC3_OPERATEX120_BI4_RST_LOCKOUTX120_BI4_RST_LOCKOUTX120_BI4_RST_LOCKOUTGUID-B7398C9F-D767-4749-8AC2-149EEE9F478D V1 ENFigure 399: ARC protection with dedicated HSOThe optional autoreclosing function is configured to be initiated by operate signalsfrom a number of protection stages through the INIT_1...5 inputs. It is possible tocreate individual autoreclose sequences for each input.The autoreclosing function can be inhibited with the INHIBIT_RECL input. Bydefault, few selected protection function operations are connected to this input. ASection 3 1MRS756378 SREF615 standard configurations268 REF615Application Manual