INSTALLATIONOPERATOR INTERFACE DEVICESI-E96-192-5A 3 - 25IIADP02 Annunciator Display PanelThe IIADP02 annunciator display panel provides 32 LEDs andpushbuttons. This panel is provided with the IIOIC422 consolemodel and can be added to the IIOIC424 panel mount model.It is not used on the IIOIC423 environmental or IIOIC421tabletop models. Each LED is assigned to a tag. Each push-button may be assigned to a display or a key macro. When atag goes into an alarm condition, the assigned LED turns on.Once the LED is activated, it will continue flashing until thealarm condition is removed. Press the pushbutton to call thedisplay or key macro assigned to it.Up to four annunciator display panels can be driven from anMKM module. Maximum cable length is 4.5 meters (15 feet).Refer to Figure 3-20 for the dipswitch configuration. Refer to theoperation and configuration instruction for more information.Figure 3-19. IIADP01 Annunciator Display Panel SW1 SettingsTP35494B .TO AUX PORT ONKEYBOARDINTERFACE BOARDP1BACK OFADP PANELADDRESSSW ITCHPC BOARDADDRESS SW ITCHSETTINGSSW 11 2 3 4 5 6 7 81 2 3 4 5 6 7 81 2 3 4 5 6 7 81 2 3 4 5 6 7 8OPENOPENOPENOPENSW 1SW 1SW 1ADP1ADP2ADP3ADP4P1SW 11948978A1P1P2P2 P2ADP2ADP3ADP41 2 3 4 5 6 7 8O PE NTable 3-6. IIADP01 Board ConnectionsCableNumber Connect From Connect To1948978A1 P1 or P2 on ADP 2boardAUX 1 port on keyboard interfaceboard, or to:P1 or P2 on ADP 3 board