2-10 InstallationLogic WiringAll logic and control connections are made at the control terminalstrip located on the motor control board. Screw type terminalsare provided for easy connection to your external control stationand meters. The control terminal strip can be divided into fourmajor categories as follows:1) Analog command inputs.2) Analog outputs.3) Opto Isolated inputs.4) Relay outputs.Analog Command InputsAn external 5kohm potentiometer can be connected at terminalsCM, VIN, and REF. The potentiometer should be connected sothat full resistance is connected from CM and REF. REF is a5VDC potentiometer reference output. The wiper of thepotentiometer should be connected at terminal VIN. The speedcommand input will be recognized at terminals CM and VIN.When using a potentiometer as the speed command, the AnalogCommand Select parameter will need to be programmed to 0 or1 and jumper J19 will need to be set properly.An external speed command of 0-5VDC, 0-10VDC, 0-20 mA, or4- 20mA can be used instead of a potentiometer at terminals CMand VIN. The positive lead should be connected at terminal VINand the negative lead should be connected at terminal CM. TheAnalog Command Select parameter should also be programmedto 0 or 1 and jumper J19 will need to be set properly.