3-22 Operation77-External Trip Select - Sets if the control will trip (Fault F07)or Coast to Stop if the condition at control terminal MOL ischanged. If set to 0 or 1, then the control will automatically shutdown indicating an External Trip (F07). If set to 2 or 3 the outputto the motor is turned off and the motor is allowed to coast (freewheel) to a stop. Even values (0 or 2) will cause terminal MOLto expect a normally low input condition while Odd values (1 or3) will cause terminal MOL to expect a normally high signalcondition. Jumper J19 sets terminal MOL for Pull-Up orPull-Down logic. The following table summarizes the availableoptions.Parameter 77-External Trip SelectJumper J19SettingValue Description / Function0 Connection of terminal V+ to terminal MOL will causean External Trip fault (F07) - Normally Open Operation.1 Removal of terminal V+ from terminal MOL will causean External Trip fault (F07) - Normally ClosedOperation.Pull-UpLogic2 Connection of terminal V+ to terminal MOL will cause aCoast to Stop command - Normally Open Operation.Logic3 Removal of terminal V+ from terminal MOL will cause aCoast to Stop command - Normally Closed Operation.0 Connection of terminal CM to terminal MOL will causean External Trip fault (F07) - Normally Open Operation.1 Removal of terminal CM from terminal MOL will causean External Trip fault (F07) - Normally ClosedOperation.Pull-DownLogic2 Connection of terminal CM to terminal MOL will cause aCoast to Stop command - Normally Open Operation.Logic3 Removal of terminal CM from terminal MOL will causea Coast to Stop command - Normally ClosedOperation.