3-24 OperationIf the inverter is set in an Auto Restart Mode and normaloperation is using input power to start and stop the motor, theinverter may be started once every two minutes. The inverter willprevent operation if more frequent starts are commanded usingline power connection.Synchro Starts - The Synchro Starts feature is desirable inapplications where the motor shaft is rotating at the time thatpower is supplied to the motor from the inverter. If enabled thecontrol will automatically sense the motor rotational frequencyand immediately output that frequency at start up.WARNING: A lightly loaded motor may suddenlyaccelerate before locking in the properspeed. Ensure that this operation will notcause injury to personnel or damage todriven equipment.Parameter 82-Start OptionsValue Description0Manual Restart. If parameter 21-OPERATING MODE = 2, 3, or 6(2-Wire Control) then Run FWD or REV commands must beremoved and then re-applied to start after application of line power.Keypad STOP Key active as a Coast to Stop command. To resetafter Keypad Coast to Stop, press Keypad STOP Key again.1Auto Restart is active after application of line power and RunCommand is given at the Control Terminal Strip. If parameter21-OPERATING MODE = 2, 3, 4, 5, 6, or 7 then Keypad STOP Keyactive as a Coast to Stop command. To reset after Keypad Coastto Stop, press Keypad STOP Key again.2Synchro Start and Manual Restart. If parameter 21- OPERATINGMODE = 2, 3, 4, 5, 6, or 7 then Keypad STOP Key active as aCoast to Stop command. To reset after Keypad Coast to Stop,press Keypad STOP Key again.3Synchro Start and Auto Restart. If parameter 21-OPERATINGMODE = 2, 3, 4, 5, 6, or 7 then Keypad STOP Key active as aCoast to Stop command. To reset after Keypad Coast to Stop,press Keypad STOP Key again.