3-14 Operationoccurrence. The elapsed time is indicated in 0.1 hourincrements with 0.9 hour maximum displayed. The two left mostdigits displayed is the fault code and the right most digits is theelapsed time.24-Analog Command Select - Selects the type of externalspeed reference command the control should be expecting tosee in your application. The possible values are 0-10V, 0-5V,0-20mA, and 4- 20mA. If long distances are required betweenthe control and the external speed command location then 0-20mA or 4-20mA should be considered since a current loopcommand scheme will allow no loss of the command signal withlong cable lengths.Also sets if the control will recognize a high value of commandsignal as a high output command or a low output command ofthe inverter. If Direct is selected the control will see a lowcommand signal as a low speed command and a high commandsignal as a high speed command. Direct is the selection used inmost applications. If Inverted is selected the control will see alow command signal as a high speed command and a highcommand signal as a low speed command.Parameter 24-ANALOG COMMAND SELECTValue Operation Analog Command Signal0 Direct 0-10 VDC, 0-5 VDC, 0-20 mA1 Inverted 10-0 VDC, 5-0 VDC, 20-0 mA2 Direct 4-20 mA3 Inverted 20-4 mA33-Preset Speed #1 - Sets the output frequency when PresetSpeed #1 is commanded at the Control Terminal Strip. Theadjustable range is 0.1-400 Hz. The factory setting is 5 Hz.34-Preset Speed #2 - Sets the output frequency when PresetSpeed #2 is commanded at the Control Terminal Strip. Theadjustable range is 0.1-400 Hz. The factory setting is 20 Hz.