Operation 3-13Parameter 75-RELAY OUTPUT SELECTValue Description0 Off1 Ready. Inactive at Fault, Low Voltage, Idle, and in ProgramMode2 Fault3 Forward and Reverse Output, Output Frequency above 0.5 Hz4 Reverse Output, Output Frequency above 0.5 Hz5 Forward Output, Output Frequency above 0.5 Hz6 Output Frequency less than 0.5 Hz7 Output at Set Frequency8 Output Frequency greater than Parameter 36-Preset Speed #4setting9 Running in Torque Limit10 Overtemperature Warning. Temperature is within 10 degreesC of maximum ratingLevel Two Parameter Adjustments02-Software Revision - A view only parameter that displays thesoftware revision code of the installed software version.03-Rated Current - A view only parameter that displays thefactory set nominal output current of the inverter. The factorysetting also serves as the 100% reference for all displayedoutput currents. The inverter continuous output current is 110%of the factory setting.08-Second Fault - A view only parameter that displays thesecond most recent fault condition before the Last Fault alongwith the elapsed time from the last restart of the control and thefault occurrence. The elapsed time is indicated in 0.1 hourincrements with 0.9 hour maximum displayed. The two left mostdigits displayed is the fault code and the right most digits is theelapsed time.09-First Fault - A view only parameter that displays the mostrecent fault condition before the Last Fault along with theelapsed time from the last restart of the control and the fault