Potentiometer Sense (DXM150 only)A potentiometer input is created from two inputs: a voltage source (pin 45) that supplies a voltage to thepotentiometer and an input sense (Potentiometer Sense) to read the resistance. See Using Universal Inputs to Reada Potentiometer (p/n b_4462775) for more information.Thermistor InputA thermistor input must use a 10k thermistor between ground and the universal input. The thermistor must be a 10kNTC (Banner model number BWA-THERMISTOR-002) or equivalent. Select the temperature conversion of degreesC (default) or degrees F by writing to the Modbus registers defined in I/O Base Boards.Example: Configure Input 1 as a Synchronous Counter1. Connect the DXM to the PC.2. Launch the DXM Configuration Software software.3. Connect to the DXM by selecting the Device > Connection Settings menu option. You may connect using eitherUSB or Ethernet.4. Select a COMM port from the drop-down list and click Connect.5. Click on the Register View tab on the left part of the page.6. Change the Source Register selection to I/O Board Registers.7. In the Write Registers area, write Modbus register 4908 to 1 to enable counting on the rising edge of the inputsignal.8. Read Modbus registers 4910 and 4911 to get the 32-bit value of the count.Example: Change Universal Input 2 to a 0 to 10 V dc Input1. Connect the DXM to the PC.2. Launch the DXM Configuration Software software.3. Connect to the DXM by selecting the Device > Connection Settings menu option. You may connect using eitherUSB or Ethernet.4. Select a COMM port from the drop-down list and click Connect.5. Click on the Register View tab on the left part of the page.6. Change the Source Register selection to I/O Board Registers.7. Write a 3 to Modbus register 3326 on Modbus Slave ID 200 (I/O board).8. Cycle power to the device.9. Using the Register View tab, read register 3326 to verify it is set to 3.Example: Change Analog Output 1 to a 0 to 10 V dc Output1. Connect the DXM to the PC.2. Launch the DXM Configuration Software software.3. Connect to the DXM by selecting the Device > Connection Settings menu option. You may connect using eitherUSB or Ethernet.4. Select a COMM port from the drop-down list and click Connect.5. Click on the Register View tab on the left part of the page.6. Change the Source Register selection to I/O Board Registers.7. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog outputjumper position.8. Write a 3 to Modbus register 4008 on Modbus Slave ID 200 (I/O board).9. Cycle power to the device.10. Using the Register View tab, read register 4008 to verify it is set to 3.Example: Change Universal Input 8 to Read a Potentiometer InputFigure 21. Default jumper position2.7 V 4.2 VPower pin 45GroundPot sense Ui8pin 35Pwr Inpin 45Vbatt1 23 45 6Sure Cross® DXM150 and 1500-Bx Wireless Controllerswww.bannerengineering.com - Tel: + 1 888 373 6767 33