Binding #—This parameter allows the user to define the Binding code within the ISM radio. Typically, you will not have toadjust this number unless you are replacing an existing Gateway or master radio.RF Ctrl—Displays the status of the ISM radio DIP switch 1 (off or on). The menu doesn't allow the user to change the DIPswitch setting through the display.7.5.2 I/O BoardUse the System Config > I/O Board submenu to change the configuration parameters for the inputs, outputs, counters, andcharger.Use the Inputs menu to change the input type. The universal inputs on the DXM are defined from the factory as sinkinginputs. To change the input type:1. Go to the System Config > I/O Board > Inputs menu.2. Select which input to change.3. Select the input type. The available parameters include the Input Type and the Counter Edge Detect.Table 26: Input parametersInput Type DescriptionSinking Discrete input, low active, 0 = ON, 1 = OFFSourcing Discrete input, high active, 1 = ON, 0 = OFFCurrent Analog input, 0–20 mAVoltage Analog input, 0–10 V DCThermistor 2* Thermistor input, 10k - J (r-t curve), beta(K) 3890Thermistor 1* Thermistor input, 10k - G (r-t curve), beta(K) 3575Counter DescriptionIn Type Sinking or sourcingCnt Rise Increment the count when the input transitions from 0 -> 1Cnt Fall Increment the count when the input transitions from 1 -> 0Use the Output menu to change the default condition, output type, and switched power voltage.Table 27: Output parametersOutput Type DescriptionDefault Force output registers to a default condition if the I/O board has not been communicated with for a user-definedtime period. The communications timeout parameter must be set to use the Default condition.Type Select the output type: NMOS Sinking, Switch Power (Swch Pwr), Analog.Voltage Outputs defined as switched power can adjust the voltage: 5 V or 16 VUse the Charger menu to change the charging algorithm for the battery. This parameter can also be set by writing Modbusregister 6071 of the I/O board. See Supplying Power from a Solar Panel on page 30.Table 28: Charger parametersCharger Parameters DescriptionDC Used when 12–24 V DC power supplies connected to the DXM power pins and the attached batteries are used asbackup batteries. This limits the current during the battery charging process. (factory default setting)Solar Select Solar when a solar panel is connected to the power pins of the DXM. Solar panels are current limited bytheir design and therefore can charge the battery without managing the input power.7.5.3 EthernetUse the Ethernet submenu to sets the IP Address, Gateway Address, and Subnet mask of the DXM's Ethernet interface.You may change these settings either from the LCD menu (System Config > Ethernet) or from the XML configuration filecreated by the DXM Configuration Software.Sure Cross® DXM150 and 1500-Bx Wireless Controllerswww.bannerengineering.com - Tel: + 1 888 373 6767 47