2610 - DISPLAY OF THE INPUTS / OUTPUTS STATUSAll variables which are controlled by the system are displayed inthis group of screens, including the status of the digital inputs, thedigital outputs and the analogue outputs, both the main board andthe installed expansion cards.This group of screens is accessed from the MAIN MENU, in E.INPUTS/OUTPUTS.● Values measured by the sensors: screens I01, I01a, I01b, I02,I03, I03a, I03b, I03c, I04a, I04b, I05a, I05c, I05e.I01S1 probeReturn temperatureprobe 16.0ßCS2 probeOutdoor temperatureprobe 20.0ßC● Cumulated operating hours by the unit and each compressor:screens I07, I07a.I07Operating hoursUnit: 00000Compress. 1-C1:00000Compress. 2-C1:00000● Digital inputs status: screen I08 (main board), screen I08b(expansion card addr.8), screen I08c (expansion card addr.9).I08Digital inputstatus (1...14):C C C C C C C C C C C C C CC: Closed contactO: Open contactI09Compressor 1 - C1 OFFCompressor 2 - C1 OFFCompressor 1 - C2 OFFCompressor 2 - C2 OFF● Digital outputs status: screens I09, I09a, I09b, I10, I11 (mainboard), screen I10b (expansion card addr.9).● Analogue outputs status: screens I12, I12a (main board), screenI12b (expansion card addr.8), screen I12c (expansion cardaddr.9).I12Outdoor damper:025%Heat valve: 000%000%: opening percentageGAVAZZI I15Voltages (V)L1-L2: 00000L2-L3: 00000L3-L1: 00000Neutral 1: 00000Neutral 2: 00000Neutral 3: 00000● Measurements performed by the energy meter (optional):screens I15, I16, I17, I18.● Electronic expansion valve(s) reading: screens I06a, I06b, I06c1,I06e, I06f, I06g, I06h.● Calculation of the cooling and heating capacities (optional):screens I18b, I18c, I18d, I18e.Refriger. power: I18bInput enthalpyvalue: 00.0 kcal/kgInput humidityvalue: 50.0 %Input temperaturevalue: 000.0 ßC11 - VERSIONS OF SOFTWARE AND HARDWARESOFTWARE V01"50FC" Contro1Version: 12.3.000 00Date: 18/12/18Bios: 6.49 30/07/18Boot: 5.00 18/07/12HARDWARE V02Board type: mPCBoard size: MediumTotal flash: 2048kBRAM: 1024kBBuilt-in type:Main cycle:09.2 cycle/s 0111msIn this group of screens O. CRTL_ID from the MAIN MENU, theSoftware version installed on the control board is provided.The second screen of this menu shows the main features of thehardware.● Cooling recovery circuit reading (optional): screens I06cr, I06fr,I06er, I05ar, I08cr, I10cr.Active recov. I06crSH: 1.4 K 21.3ßC0480stp C1100% 09.5bgEDV: 09.0ßC 29.5bgOn 49.4ßCValve A I06aSH: 007.6 K 0012.4ßC0000stp C1000% 08.3barg C2EDV: 04.8ßC 27.3bgOn 46.2ßC