4016 - LIST OF CONTROL PARAMETERS16.1. Parameters with “Level of access 1”Parameters of “Unit On/Off”Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W Add.BMSPM01 SYS_ONSelection of the unit ON/OFF by keyboard or remote:0: Switch-off (Off)1: Switch-on (On)0 0 1 --- Digital R/W 65Parameters of “Cooling/Heating”Screen Parameter Description of the parameter Value Min. Max. UOM Tipo R/W Add.BMSFC01 SEL_FRIO_CALORProcedures for the selection of the COOLING/HEATING mode:0: by keyboard1: unused2: auto3: only ventilation0 0 3 --- Integer R/W 59FC01 MODO_FRIO_CALOR_AUTOCOOLING/HEATING selection in AUTO:0: by indoor temperature1: by outdoor temperature1 0 1 --- Digital R/W 232FC01 CALOR_FRIO_PANELCOOLING/HEATING selection by keyboard:0: HEATING (winter)1: COOLING (summer)1 --- Digital R/W 66FC01 SET_TEMP_EXT_CAMBIO_FRIO Outdoor temperature setpoint for change to COOLING mode (in AUTOmode) 22.0 99.9 99.9 °C Analog. R/W 223FC01 SET_TEMP_EXT_CAMBIO_CALOR Outdoor temperature setpoint for change to HEATING mode (in AUTOmode) 20.0 99.9 99.9 °C Analog. R/W 222FC01 PGD1_bloqueado_SEL_FRIO_CALOREnabling of the blocking of summer / winter selection in the Graphic terminal(so that the final user cannot change it) 0 0 1 --- Digital R/W 240Parameters of “Setpoint”Screen Parameter Description of the parameter Value Min. Max. UOM Type R/W Add.BMSS01 SET_POINT_TEMP_FRIO Temperature setpoint in COOLING mode (summer) 26.0 LIM_INF_TEMP_FRIOLIM_SUP_TEMP_FRIO °C Analog. R/W 15S01 SET_POINT_TEMP_CALOR Temperature setpoint in HEATING mode (winter) 21.0 LIM_INF_TEMP_CALORLIM_SUP_TEMP_CALOR °C Analog. R/W 16S02 SET_POINT_HUM Indoor humidity setpoint 50.0 LIM_INF_HUM LIM_SUP_HUM %rH Analog. R/W 18S02 H A B _ S O N D A _ H U M _ I N T _VIRTUAL Enabling the pLAN indoor humidity probe 0 --- Digital RS03 SET_COMPRESOR_EN_FRIO Calculation of setpoints: Setpoint in COOLING mode(summer) + Dead Zone / 2 0.0 0.0 0.0 °C Analog. RS03 SET_COMPRESOR_EN_CALOR Calculation of setpoints: Setpoint In HEATING mode(winter) + Dead Zone / 2 0.0 0.0 0.0 °C Analog. RS03 SET_TEMP_COMPRESOR Current selection of the setpoint 0.0 0.0 0.0 °C Analog. RS03 SET_RES_EN_FRIO Calculation of setpoints: Setpoint of the electrical heatersin COOLING mode 0.0 0.0 0.0 °C Analog. RS03 SET_RES_EN_CALOR Calculation of setpoints: Setpoint of the electrical heatersin HEATING mode 0.0 0.0 0.0 °C Analog. RS03 SET_TEMP_RES Current selection of setpoint for electrical heaters 0.0 0.0 0.0 °C Analog. RS03 SET_VLV_CALOR_EN_FRIO Calculation of setpoints: Setpoint of the hot water coil inCOOLING mode 0.0 0.0 0.0 °C Analog. R/WS03 SET_VLV_CALOR_EN_CALOR Calculation of setpoints: Setpoint of the hot water coil inHEATING mode 0.0 0.0 0.0 °C Analog. R/WS03 SET_VLV_CALOR Current selection of setpoint for the hot water coil 0.0 0.0 0.0 °C Analog. R/WS03 SET_FCOOL_VER Calculation of setpoints: free-cooling in summer 00.0 -99.9 99.9 --- Integer RS03 SET_FCOOL_INV Calculation of setpoints: free-cooling in winter 00.0 -99.9 99.9 --- Integer RS03 SET_FHEAT Calculation of setpoints: free-heating 00.0 -99.9 99.9 --- Integer RS04 SET_IMPULSION_FRIO_CAL Supply setpoint calculated in COOLING mode 7.0 0.0 30.0 °C Analog. R 122S04 SET_IMPULSION_CALOR_CAL Supply setpoint calculated in HEATING mode 45.0 0.0 55.0 °C Analog. R 121GENUITAHCCONFIGBSETPOINTC