6316.3. Parameters with “Level of access 3”16 - LIST OF CONTROL PARAMETERSParameters of “Manufacturer”Screen Parameter Description of the parameter Value Min. Max. UOM Tipo R/W Add.BMSCU01 MODELO_EQUIPO Unit model 0 0 40 --- Integer R/W 58CU01 TIPO_EQUIPO Selection of the unit type (0=air-air) 0 0 1 --- Integer R/W 182CU01 HAB_BOMBA_CALOR Enable the operation as heat-pump (0=cooling only; 1=heat pump) 1 0 1 --- Digital R/W 45CU01 NUM_WO_DIG_1 Work order number of the unit (digit 1) 0 0 9 --- Integer R/W 185CU01 NUM_WO_DIG_2 Work order number of the unit (digit 2) 0 0 9 --- Integer R/W 186CU01 NUM_WO_DIG_3 Work order number of the unit (digit 3) 0 0 9 --- Integer R/W 187CU01 NUM_WO_DIG_4 Work order number of the unit (digit 4) 0 0 9 --- Integer R/W 188CU01 NUM_WO_DIG_5 Work order number of the unit (digit 5) 0 0 9 --- Integer R/W 189CU01 NUM_WO_DIG_6 Work order number of the unit (digit 6) 0 0 9 --- Integer R/W 190CU01 NUM_WO_DIG_7 Work order number of the unit (digit 7) 0 0 9 --- Integer R/W 191CU01 NUM_WO_DIG_8 Work order number of the unit (digit 8) 0 0 9 --- Integer R/W 192CU02 NUM_COMP_CIRCNumber of compressor:0: without compr.2: 2 compressors / 1 circuit6: 4 compressors / 2 circuits1 0 7 --- Integer R/W 60CU02 HAB_UNICO_VOL_AIRE_EXT Enable the single volume of outdoor air (0: no ; 1: yes) 1 0 1 --- Digital R/W 57CU02a HAB_COMPRESOR_REC Enable de cooling recovery circuit 0 0 1 --- Digital R/WCU02a MIN_APERTURA_ON_REC % of minimum opening of outdoor damper to allow the start of the recoverycompressor 10 0 99 % Integer R/W 68CU02a TIME_MIN_APERTURA_ON_REC Time with minimum opening of outdoor damper to allow the start of the recoverycompressor 90 0 999 s Integer R/W 9CU02a HAB_BOMBA_CALOR_COMP_RECCompressor recovery - heat pump0: Compressor recovery + cooling only;1: Compressor recovery + heat pump1 0 1 --- Digital R/W 203CU03 CONF_OUT07Element connected on the digital output OUT07:0: Humidifier1: Pump of the HWC circuit2: Pump of the boiler circuit3: Alarm4: Inverter compressor5: Heat recovery wheel3 0 5 --- Integer R/W 117CU03 HAB_OUT07_BOMBA_BAC Enable the pump and the HWC valve depending on the low outdoor temp. 0 0 1 --- Digital R/WCU03 SET_ON_VALV_CALOR_POR_BAJA_TEXTSetpoint to start-up the pump and the HWC valve depending on the low outdoortemperature 4.0 -10.0 10.0 °C Analog. R/W 82CU03 MIN_APERTURA_VALV_CALOR Minimum opening of the HWC valve with low outdoor temp. and unit ON 10 0 100 % Integer R/W 211CU03 TIME_RET_OFF_BOMBA_BAC Delay time to stop of the HWC pump 60 0 999 s Integer R/W 210CU03 HAB_OUT07_BOMBA_BAC Enable the pump of the boiler circuit depending on the low outdoor temp. 0 0 1 --- Digital R/WCU03 SET_ON_VALV_CALOR_POR_BAJA_TEXTSetpoint to start-up the pump of the boiler circuit depending on the low outdoortemperature 4.0 -10.0 10.0 °C Analog. R/WCU03 MIN_APERTURA_BOILER Minimum opening of the boiler with low outdoor temperature and unit ON 10 0 100 % Integer R/WCU03 TIME_RET_OFF_BOMBA_BOILER Delay time to stop of the pump of the boiler circuit 60 0 999 s Integer R/WCU03 HAB_REC_ROTATIVO_VARIABLE Enable the rotary heat exchanger with variable wheel 0 0 1 --- Digital R/W 247CU03 MIN_APERTURA_ON_REC % of minimum opening of outdoor damper to allow the start of the rotary heatexchanger 10 0 99 % Integer R/W 68CU03 TIME_MIN_APERTURA_ON_REC Time with minimum opening of outdoor damper to allow the start of the rotaryheat exchanger 90 0 999 s Integer R/W 9CU03 H A B _ C O M P U E R T A _ C O N _DESESCARCHEEnable the opening of the outdoor damper during defrosting with rotary heatexchanger 0 0 1 --- Digital R/WCU03 TIME_ON_VEXT_INI_DES Running time of the outdoor fan at the start of the defrosting 45 0 120 s Integer R/W 185CU03 Inverter_Power_Min Minimum power of the inverter compressor 30 0 99 --- Integer R/WCU03 IS_OUT_INVERTER Lower threshold of the inverter compressor 0.0 0.0 10.0 --- Analog. R/WCU03 FS_OUT_INVERTER Upper threshold of the inverter compressor 5.0 0.0 10.0 --- Analog. R/WCU03a CONF_OUT01_MOD_N8Element on the digital output 01 of the pCOe expansion card with addr.8:0: Humidifier1: Pump of the HWC circuit2: Pump of the boiler circuit3: Alarm4: Inverter compressor5: Heat recovery wheel6 0 6 --- Integer R/W 218CU03a HAB_OUT01_N8_BOMBA_BAC Enable the pump and the HWC valve depending on the low outdoor temp. 0 0 1 --- Digital R/WCU03a SET_ON_VALV_CALOR_POR_BAJA_TEXTSetpoint to start-up the pump and the HWC valve depending on the low outdoortemperature 4.0 -10.0 10.0 °C Analog. R/W 82CU03a MIN_APERTURA_VALV_CALOR Minimum opening of the HWC valve with low outdoor temp. and unit ON 10 0 100 % Integer R/W 211CU03a TIME_RET_OFF_BOMBA_BAC Delay time to stop of the HWC pump 60 0 999 s Integer R/W 210CU03a HAB_OUT07_BOMBA_BAC Enable the pump of the boiler circuit depending on the low outdoor temp. 0 0 1 --- Digital R/WCU03a SET_ON_VALV_CALOR_POR_BAJA_TEXTSetpoint to start-up the pump of the boiler circuit depending on the low outdoortemperature 4.0 -10.0 10.0 °C Analog. R/WCU03a MIN_APERTURA_BOILER Minimum opening of the boiler with low outdoor temperature and unit ON 10 0 100 % Integer R/Wa.Unit Config.GENCONFIGG