12Performance data (cont)-Standard PSC indoor motorCOOLING EXTENDED PERFORMANCE TABLEHEATING EXTENDED PERFORMANCE TABLE -10–20HEATING EXTENDED PERFORMANCE TABLE 30–60*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.See Legend and Notes on page 17.50JZ030 COOLING PERFORMANCE TABLETemp (F)Outdoor AirEnteringCondenserEvaporator Air—CFM/BF875/0.08 1000/0.09 1125/0.10Evaporator Air — Ewb (F)62 63* 67 72 62 63* 67 72 62 63* 67 7275 TC 28.1 28.5 30.8 33.2 29.1 29.5 31.8 33.7 30.5 30.5 32.8 34.5SHC 26.0 21.2 21.8 17.4 28.2 22.8 23.3 18.0 30.5 25.3 25.3 18.9kW 2.17 2.25 2.19 2.21 2.18 2.26 2.20 2.21 2.19 2.26 2.20 2.2285 TC 26.3 26.8 29.6 32.1 27.0 27.7 30.5 32.8 29.4 29.0 31.4 33.4SHC 24.7 20.4 21.5 17.1 26.6 22.0 23.1 17.9 29.4 25.1 25.3 18.8kW 2.39 2.49 2.44 2.45 2.38 2.50 2.44 2.45 2.43 2.52 2.44 2.4695 TC 24.9 25.4 27.9 30.9 25.7 25.9 28.9 31.5 28.3 27.0 29.8 32.1SHC 23.7 19.6 21.0 16.7 25.7 21.1 22.7 17.5 28.3 24.2 25.4 18.6kW 2.65 2.75 2.69 2.71 2.67 2.76 2.71 2.71 2.71 2.78 2.70 2.72105 TC 23.4 22.2 26.1 29.2 24.3 23.1 26.9 29.8 26.5 25.0 27.9 30.5SHC 22.5 17.2 20.2 16.2 24.3 19.0 21.9 17.1 26.5 22.8 24.7 18.4kW 2.92 2.99 2.98 2.99 2.94 3.02 2.99 3.00 2.98 3.06 2.99 3.00115 TC 21.7 19.0 24.2 27.4 22.9 20.3 24.9 27.8 24.7 22.9 25.8 28.5SHC 21.4 14.7 19.4 15.5 22.9 16.8 21.0 16.4 24.7 21.8 23.8 17.9kW 3.24 3.23 3.28 3.28 3.25 3.27 3.29 3.30 3.29 3.37 3.30 3.30125 TC 19.9 19.3 22.1 25.1 21.3 19.9 22.6 25.5 22.9 21.0 23.5 26.1SHC 19.9 17.4 18.1 14.6 21.3 18.5 19.8 15.6 22.9 21.0 22.7 17.1kW 3.57 3.65 3.60 3.62 3.58 3.67 3.61 3.62 3.62 3.71 3.62 3.6250JZ030ReturnAir (F db) CFM (Standard Air) Air Temperature Entering Outdoor Coil (F db at 70% rh)-10 0 10 17 2060875 TC 7.7 6.5 10.8 9.2 14.0 12.9 16.6 15.2 17.9 16.1kW 1.93 2.00 2.08 2.08 2.111000 TC 7.8 6.6 11.0 9.3 14.2 13.0 16.8 15.3 18.0 16.2kW 1.90 1.97 2.04 2.04 2.071125 TC 7.8 6.6 11.0 9.4 14.3 13.1 16.9 15.4 18.1 16.3kW 1.89 1.94 2.00 2.00 2.0370875 TC 6.9 5.9 10.1 8.6 13.3 12.2 15.8 14.4 17.0 15.4kW 2.11 2.20 2.29 2.35 2.371000 TC 7.2 6.1 10.3 8.8 13.5 12.4 16.1 14.7 17.3 15.6kW 1.98 2.11 2.24 2.24 2.271125 TC 7.1 6.0 10.3 8.8 13.6 12.5 16.2 14.8 17.4 15.7kW 2.09 2.15 2.21 2.20 2.2380875 TC 6.1 5.1 9.3 7.9 12.5 11.5 15.0 13.7 16.2 14.6kW 2.30 2.40 2.51 2.59 2.601000 TC 6.1 5.2 9.4 8.0 12.7 11.6 15.2 13.9 16.4 14.8kW 2.28 2.37 2.46 2.53 2.541125 TC 6.2 5.3 9.5 8.1 12.8 11.8 15.5 14.1 16.7 15.0kW 2.28 2.35 2.43 2.42 2.4550JZ030ReturnAir (F db) CFM (Standard Air) Air Temperature Entering Outdoor Coil (F db at 70% rh)30 40 47 50 6060875 TC 22.0 19.2 26.3 26.3 29.7 29.7 30.7 30.7 35.0 35.0kW 2.22 2.35 2.46 2.48 2.611000 TC 22.1 19.4 26.5 26.5 29.7 29.7 30.8 30.8 35.2 35.2kW 2.16 2.28 2.36 2.39 2.511125 TC 22.2 19.5 26.6 26.6 29.8 29.8 30.9 30.9 35.2 35.2kW 2.12 2.22 2.30 2.32 2.4370875 TC 21.1 18.5 25.7 25.7 29.0 29.0 30.4 30.4 34.7 34.7kW 2.43 2.58 2.70 2.76 2.881000 TC 21.3 18.7 25.9 25.9 29.3 29.3 30.6 30.6 35.1 35.1kW 2.37 2.50 2.62 2.66 2.781125 TC 21.4 18.8 26.0 26.0 29.5 29.5 30.8 30.8 35.2 35.2kW 2.32 2.44 2.55 2.58 2.7080875 TC 20.4 17.9 25.0 25.0 28.2 28.2 29.7 29.7 34.5 34.5kW 2.65 2.82 2.95 3.02 3.231000 TC 20.6 18.0 25.3 25.3 28.5 28.5 29.9 29.9 34.7 34.7kW 2.59 2.74 2.86 2.92 3.091125 TC 20.7 18.2 25.4 25.4 28.8 28.8 30.2 30.2 34.9 34.9kW 2.54 2.67 2.79 2.84 2.99