21Balance Point Worksheet010203040506070-10 0 10 17 20 30 40 47 50 60Outdoor Air Temp (Deg F)Building Heat Loss, 1000BTUHUnit Integrated Heating Capacity (x1000BTUH)024030036042048060Based on Indoor Entering Air of 70 F and Rated CFMCondensate trap — A 2-in. condensate trap must be fieldsupplied.Ductwork — Secure downflow discharge ductwork to roofcurb. For horizontal discharge applications, attach ductworkto unit with flanges.To convert a unit to downflow discharge — Units areequipped with factory-installed inserts in the downflowopenings. Remove the inserts similar to removing anelectrical knock-out. Leave on duct covers to seal thehorizontal discharge openings in the unit. Units installed inhorizontal discharge orientation do not require duct covers.Maximum cooling airflow — To minimize the possibilityof condensate blow-off from the evaporator, airflow throughthe units should not exceed 450 cfm/ton.Minimum cooling airflow — The minimum cooling airflowis 350 cfm/ton.Minimum cooling ambient operating temperature — Allstandard units have a minimum ambient operatingtemperature of 40°F. Units with the ICM Indoor Motor FIOPhave a minimum cooling outdoor operating temperature of55°F. With accessory low ambient temperature kit, units canoperate at temperatures down to 0°F.Maximum operating outdoor air temperature — Maximumoutdoor operating air temperature for cooling is 125°F.Application data1” MIN.2” MIN.TRAPOUTLET