3ARI* capacities COOLING CAPACITIES AND EFFICIENCIES50JZ ICM FIOP RATINGSUNIT50JZNOMINALTONSSTANDARDCFMNET COOLINGCAPACITIES(Btuh)SEER†SOUNDRATINGS‡(dB)024 2 800 24,000 12.0 72030 2-1/2 1000 29,000 12.0 72036 3 1200 36,000 12.0 77042 3-1/2 1400 41,000 12.0 73048 4 1600 47,500 12.0 79060 5 1750 59,000 12.0 79COOLING HEATINGUNIT50JZ“A”**CAPACITY“A”**EER SEER HIGH CAPBTUH@47°FLOW CAPBTUH@17°FHIGH COP@47°FLOW COP@17°F HSPF024 24,000 11.2 12.7 23,800 13,000 3.2 2.1 7.2030 29,000 11.0 12.7 28,000 15,400 3.2 2.1 7.2036 36,000 10.8 12.3 34,400 18,000 3.2 2.0 7.2042 41,000 11.0 12.5 39,400 21,400 3.2 2.0 7.2048 47,500 10.8 12.3 43,600 23,000 3.2 2.1 7.2060 59,000 10.2 12.3 54,800 30,800 3.2 2.1 7.2HEATING CAPACITIES AND EFFICIENCIESUNIT50JZHIGH HEAT CAPACITY(BTUH) @ 47°FHIGH HEAT COP@ 47°FLOW HEAT CAPACITY(BTUH) @ 17°FLOW HEAT COP@ 17°F HSPF†024 23,800 3.0 13,000 2.0 7.0030 28,200 3.1 15,600 2.0 7.1036 34,400 3.2 18,000 2.0 7.2042 40,000 3.2 22,000 2.0 7.2048 44,000 3.1 23,600 2.0 7.2060 55,000 3.1 31,000 2.0 7.2TTLEGENDdB — Sound Levels (decibels)db — Dry BulbSEER — Seasonal Energy Efficiency Ratiowb — Wet BulbCOP — Coefficient of PerformanceHSPF — Heating Season Performance Factor* Air Conditioning & Refrigeration Institute.** “A” capacity– 80°F indoor db/67°F indoor wb & 95°F outdoor db.† Rated in accordance with U.S. Government DOE (Department ofEnergy) test procedures and/or ARI Standard 210/240-94.‡ Tested in accordance with ARI Standard 270-95 (not listed in ARI).NOTES:1. Ratings are net values, reflecting the effects of circulating fan heat.Ratings are based on:Cooling Standard: 80°F db, 67°F wb indoor entering-air tempera-ture and 95°F db outdoor entering-air temperature.2. Before purchasing this appliance, read important energy cost andefficiency information available from your retailer.Model number nomenclature50JZ 024 3 VSModel Number50JZ – SinglePackaged HeatPumpNominal Cooling Capacity024 – 2 ton030 – 2.5 ton036 – 3 ton042 – 3.5 ton048 – 4 ton060 – 5 tonV-Ph-Hz3 – *280/230-1-605 – 208/230-3-606 – 460-3-60 AL — AluminumCU — CopperOptionsBT – AL evap, vinyl condensCC – AL evap, CU condensCU – CU evap & condensVS – Variable speed (VS) UnitVT – VS, AL evap, vinyl condensVC – VS, AL evap, CU condensVU – VS, CU evap & condensOnly used if ordering an option*Variable speed models are only available in208/230-1-60 (3)