52Table 27 – RTU Open Controller Inputs and OutputsPOINT NAME BACnet OBJECTNAME TYPE OF I/O CONNECTIONPIN NUMBER(S) CHANNEL DESIGNATIONDEDICATED INPUTSSpace Temp / Zone Temp zone_temp AI (10K Thermistor) J20--- 1 and 2 Analog Input 10Supply Air Temperature sa_temp AI (10K Thermistor) J2--- 1 and 2 Analog Input 6Outside Air Temperature oa_temp AI (10K Thermistor) J2--- 3 and 4 Analog Input 7Space Temperature Offset Pot stpt_adj_offset AI (100K Potentiometer) J20--- 3 and 4 Analog Input 11Safety Chain Feedback safety_status BI (24 VAC) J1--- 9 Binary Input 4Compressor Safety Status (1) comp_status BI (24 VAC) J1--- 2 Binary Input 3Fire Shutdown Status firedown_status BI (24 VAC) J1--- 10 Binary Input 5Enthalpy Status enthalpy_status BI (24 VAC) J2--- 6 and 7 Binary Input 8Humidistat Input Status humstat_status BI (24 VAC) J5--- 7 and 8 Binary Input 9Zone Temperature n/a n/a J13--- 1--- 4 RnetCONFIGURABLE INPUTS (4)Indoor Air CO2 iaq AI (4--- 20 mA)J4---2 and 3 or J4---5 and 6Analog Input 2Outdoor Air CO2 oaq AI (4--- 20 mA) Analog Input 1Space Relative Humidity space_rh AI (4--- 20 mA) Analog Input 10Supply Fan Status (2) sfan_status BI (24 VAC)J5---1 and 2 or J5---3 and 4,J5---5 and 6 or J5---7 and 8 (3)Binary Input 3, 5, 8, or 9, except where intrinsic input is usedFilter Status (2) filter_status BI (24 VAC) Binary Input 3, 5, 8, or 9, except where intrinsic input is usedDoor Contact (2) door_contact_status BI (24 VAC) Binary Input 3, 5, 8, or 9, except where intrinsic input is usedRemote Occupancy input (2) occ_contact_status BI (24 VAC) Binary Input 3, 5, 8, or 9, except where intrinsic input is usedIGC input (2) igcovr_status BI (24 VAC) Binary Input 9. Mandatory input on gas heat units.OUTPUTSEconomizer Output econ_output AO (4--- 20mA) J2--- 5 Analog Output 1Supply Fan VFD vfd_output AO (2--- 10Vdc) J22--- 1 and 2 Analog Output 2Supply Fan Relay sfan BO Relay (24VAC, 1A) J1--- 4 Binary Output 1 (G)Cool 1 Relay State comp_1 BO Relay (24VAC, 1A) J1--- 8 Binary Output 5 (Y1)Cool 2 Relay State comp_2 BO Relay (24VAC, 1A) J1--- 7 Binary Output 4 (Y2)Cool 3 Relay State comp_3 BO Relay (24VAC, 1A) J11--- 5 and 6 Binary Output 7 (Y3)Heat 1 Relay State heat_1 BO Relay (24VAC, 1A) J1--- 6 Binary Output 3 (W1)Heat 2 Relay State heat_2 BO Relay (24VAC, 1A) J1--- 5 Binary Output 2 (W2)Power Exhaust Relay State pexh BO Relay (24VAC, 1A) J11--- 2 and 3 (N.O.) Binary Output 8 (PE)Dehumidification Relay dehum BO Relay (24VAC, 1A) J11--- 7 and 8 (N.O.) Binary Output 6LEGENDAI --- Analog InputAO --- Analog OutputBI --- Binary InputBO --- Binary Output(1) Safety Chain Feedback: 24 vac required at this terminal to provide “Run Enable” status. See Input/Output section for additional instructions.(2) These inputs are configurable. If installed, they take the place of the default input on the specific channel. See appropriate Input Configuration Section for wiring and setup instructions.(3) Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5--- 5 = J1--- 2 are used for field--- installation.(4) Refer to the input configuration and accessory sections of the RTU Open Multi ---Protocol Controller Controls, Start ---Up, Operation and Troubleshooting manual for more detail.The RTU Open controller requires the use of a Carrierspace sensor. A standard thermostat cannot be used withthe RTU Open controller system.Supply Air Temperature (SAT) Sensor —On FIOP--equipped 50TCQ unit, the unit is supplied with asupply--air temperature (SAT) sensor (33ZCSENSAT). Thissensor is a tubular probe type, approx 6--inches (152 mm) inlength. It is a nominal 10--k ohm thermistor.The SAT is factory--wired. The SAT probe is wire--tied tothe supply--air opening (on the horizontal opening end) inits shipping position. Remove the sensor for installation.Re--position the sensor in the flange of the supply--airopening or in the supply air duct (as required by localcodes). Drill or punch a 1 / 2 --in. hole in the flange or duct.Use two field--supplied, self--drilling screws to secure thesensor probe in a horizontal orientation. See Fig. 49.Outdoor Air Temperature (OAT) Sensor —The OAT is factory--mounted in the EconoMi$erR2 (FIOPor accessory). It is a nominal 10k ohm thermistor attachedto an eyelet mounting ring.EconoMi$er2 —The RTU Open controller is used with EconoMi$er2(option or accessory) for outdoor air management. Thedamper position is controlled directly by the RTU Opencontroller; the EconoMi$er2 unit has no internal logicdevice.Outdoor air management functions can be enhanced withfield--installation of these accessory control devices:Enthalpy control (outdoor air or differential sensors)Space CO2 sensorOutdoor air CO2 sensorField ConnectionsField connections for accessory sensors and input devicesare made the RTU Open controller, at plugs J1, J2, J4, J5,J11 and J20. All field control wiring that connects to theRTU Open controller must be routed as shown in Fig. 38.This routing provides the UL required clearance betweenhigh-- and low--voltage wiring. Connect to the wires to theremovable PCB connectors and then reconnect theconnectors to the board.