131APPENDIX C — CCN TABLES (cont)SERVICE CONFIGURATION TABLES (cont)*Not supported.*Not supported. Must be configured at default.NOTE: This table shall be downloadable at any time. However, modified value shall not be used by tasks until the unit is in OFF state. This shall not apply to the Varifangains that shall be modified at any time and used immediately by the head pressure control tasks even if the unit is in operation.*Not supported.NOTE: This table shall be used for purposes of transplanting the devices on time in the event of a module hardware failure or software upgrade via downloading. It shallbe usable only if all items are still null. Afterwards, its access shall be denied.TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME WRITE STATUSMAINTCFG MAINTENANCE CONFIGServicing Alert Enable/Disable Disable s_alertRefrigerant Charge Ctrl Enable/Disable Disable charge_cWater Loop Control Enable/Disable Disable wloop_cCPump 1 Ctl Delay (days) 0-1000 0 cpump1_cCPump 2 Ctl Delay (days) 0-1000 0 cpump2_cHPump 1 Ctrl Delay (days)* 0-1000 0 hpump1_cHPump 2 Ctrl Delay (days)* 0-1000 0 hpump2_cWater Filter Ctrl (days) 0-1000 0 wfilte_cOil Filter A Ctrl (days) 0 to 1000 0 oilfia_cOil Filter B Ctrl (days) 0 to 1000 0 oilfib_cOil Filter C Ctrl (days) 0 to 1000 0 oilfic_cTABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME WRITE STATUSSERVICE1 Cooler Fluid Type 1/21=Water2=Brine1 flui_typFlow Switch SP* 0-60 1 flow_spBrine Freeze Setpoint –20.0-34.0 34 °F freezespBrine Minimum Fluid Temp 10.0-34.0 38 °F mini_lwtCondenser Fluid Type 1/21=Water2=Brine1 cond_typEntering Fluid Control Yes/No No ewt_optProp PID Gain Varifan –20.0-20.0 2.0 hd_pgInt PID Gain Varifan –5.0-5.0 0.2 hd_igDeri PID Gain Varifan –20.0-20.0 0.4 hd_dgMaximum Ducted Fan Speed 20-100 100 % fan_maxEXV A Superheat Setpoint 12.6-44 14.4 ^F sh_sp_aEXV B Superheat Setpoint 12.6-44 14.4 ^F sh_sp_bEXV C Superheat Setpoint 12.6-44 14.4 ^F sh_sp_cPinch offset circuit A –3.0-3.0 0 ^F p_ofst_aPinch offset circuit B –3.0-3.0 0 ^F p_ofst_bPinch offset circuit C –3.0-3.0 –3.6 ^F p_ofst_cEXV MOP Setpoint 40-55 62 °F mop_spHigh Pressure Threshold 200-290 275.5 psi hp_thCooler Heater Delta Spt 1-6 2 ^F heaterspAuto Start When SM Lost Enable/Disable Disable auto_sm3way Valve Min Position 0-50 0 % min_3w3way Valve Max Position 20-100 100 % max_3wEconomizer SH Setpoint A 5-15 10.8 ^F esh_sp_aEconomizer SH Setpoint B 5-15 10.8 ^F esh_sp_bEconomizer SH Setpoint C 5-15 10.8 ^F esh_sp_cFast Loading Sequence 0-4 0 fastloadEWT Probe on Cir A Side Yes/No Yes ewt_cirATABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUSTABLE TO BE USED FOR RUN TIMES UPDATE IN CASE OF CONTROL RETROFITUPDHRFAN*Free Cooling A Pump Hours 0 hours hr_fcp_aFree Cooling B Pump Hours 0 hours hr_fcp_bCircuit A Defrost Number 0 nb_def_aCircuit B Defrost Number 0 nb_def_bCircuit A Fan #1 Hours 0 hours hr_fana1Circuit A Fan #2 Hours 0 hours hr_fana2Circuit A Fan #3 Hours 0 hours hr_fana3Circuit A Fan #4 Hours 0 hours hr_fana4Circuit A Fan #5 Hours 0 hours hr_fana5Circuit A Fan #6 Hours 0 hours hr_fana6Circuit A Fan #7 Hours 0 hours hr_fana7Circuit A Fan #8 Hours 0 hours hr_fana8Circuit A Fan #9 Hours 0 hours hr_fana9Circuit A Fan #10 Hours 0 hours hrfana10Circuit B Fan #1 Hours 0 hours hr_fanb1Circuit B Fan #2 Hours 0 hours hr_fanb2Circuit B Fan #3 Hours 0 hours hr_fanb3Circuit B Fan #4 Hours 0 hours hr_fanb4Circuit B Fan #5 Hours 0 hours hr_fanb5Circuit B Fan #6 Hours 0 hours hr_fanb6Circuit B Fan #7 Hours 0 hours hr_fanb7Circuit B Fan #8 Hours 0 hours hr_fanb8Circuit B Fan #9 Hours 0 hours hr_fanb9Circuit B Fan #10 Hours 0 hours hrfanb10Circuit C Fan #1 Hours 0 hours hr_fanc1Circuit C Fan #2 Hours 0 hours hr_fanc2Circuit C Fan #3 Hours 0 hours hr_fanc3Circuit C Fan #4 Hours 0 hours hr_fanc4Circuit C Fan #5 Hours 0 hours hr_fanc5Circuit C Fan #6 Hours 0 hours hr_fanc6Circuit C Fan #7 Hours 0 hours hr_fanc7Circuit C Fan #8 Hours 0 hours hr_fanc8