i-Vu® XT Router (drv_gen5) CARRIER CORPORATION ©2022Installation and Start-up Guide 38 All rights reservedSYS (System Status) Tricolor LEDColor Pattern Condition Message in ModuleStatusPossible SolutionRed 2 blink Restarting after an abnormal exit Auto restart delay due tosystem error on startupAfter 5-minute delay hasexpired, if condition occursagain then cycle powerRed 4 blink Firmware image is corrupt Firmware error Download driver againRed FastblinkFirmware error has caused thefirmware to exit and restartFatal error detected No action requiredGreen 1 blink No errors Operational No action requiredGreen 2 blink Download of driver is in progress Download in progress No action requiredGreen 3 blink BACnet Device ID is not set Download required Download the routerGreen FastblinkInstallation of recently downloadeddriver is occurringN/A No action requiredBlue On Router is starting up N/A No action requiredBlue SlowblinkLinux (operating system) is starting up N/A No action requiredBlue FastblinkLinux is running but it could not startthe firmware applicationN/A Download driverOrange slowblinki-Vu® XT Router with drv_gen5 driver isstartingN/A No action requiredOrange 2 blink i-Vu® XT Router with drv_gen5 driverhas started but is not yet able todetermine system and network statusN/A No action requiredTo get a Module Status reportA Module Status report provides information about the router and verifies proper network communication with therouter. You can get this report:• In the i-Vu® application—Right-click the router on the navigation tree, then select Module Status.• In the controller setup interface through the Service Port—Click and select Modstat from the drop-downlist.See Appendix - Module Status field descriptions (page 43).