SiBE07-618_C Main FunctionsFunction and Control 211.4 Program Dry OperationOutline Program dry operation removes humidity while preventing the room temperature from lowering.Since the microcomputer controls both the temperature and airflow rate, the temperatureadjustment and fan adjustment buttons are inoperable in this mode.Detail The microcomputer automatically sets the temperature and airflow rate. The difference betweenthe room thermistor temperature at start-up and the target temperature is divided into twozones. Then, the unit operates in the dry mode with an appropriate capacity for each zone tomaintain the temperature and humidity at a comfortable level.Room thermistortemperature at start-upTarget temperatureXThermostat OFF pointYThermostat ON pointZ24ºC or moreRoom thermistortemperature at start-upX – 2.5ºCX – 0.5ºCorY + 0.5ºC (zone B)continues for 10 min.23.5ºCX – 2.0ºCX – 0.5ºCorY + 0.5ºC (zone B)continues for 10 min.~18ºC18ºC X – 2.0ºCX – 0.5ºC = 17.5ºCorY + 0.5ºC (zone B)continues for 10 min.17.5ºC~ZXYZone B Zone BZone A = Thermostat OFFZone C = Thermostat ON+0.5ºC(R11581)