SiBE07-618_C Control SpecificationFunction and Control 333.3.4 3-minute StandbyTurning on the compressor is prohibited for 3 minutes after turning it off.(Except when defrosting.)3.3.5 Compressor Protection FunctionWhen turning the compressor from OFF to ON, the upper limit of frequency is set as follows.(The function is not activated when defrosting.)3.4 Discharge Pipe Temperature ControlOutline The discharge pipe temperature is used as the internal temperature of the compressor. If thedischarge pipe temperature rises above a certain level, the upper limit of frequency is set tokeep this temperature from going up further.DetailFCG3(Hz)Frequency(Sec.)TimeFCG2FCG1TCG1 TCG2 TCG3(R10540)FCG 1FCG 2FCG 3TCG 1TCG 2TCG 3557085120200470HzsecondsZone ControlStop zone When the temperature reaches the stop zone, the compressor stops.Drooping zone The timer starts, and the frequency is drooping.Keep zone The upper limit of frequency is kept.Up zone The upper limit of frequency is increased.Reset zone The upper limit of frequency is canceled.(°C) 110(°C) 103(°C) 101.5(°C) 100(°C) 95(R12014)˚C˚C˚CDischarge pipetemperatureStop zone ˚CDrooping zoneKeep zoneUp zoneReset zone ˚C