3/9Breadcrumb Field code Setting name Range, stepDefault valueDate ValueField settings table Installer setting at variance withdefault valueA.2.1.5 [5-0D] R/W 0: 1P,(1/2)1: 1P,(1/1+2) (*3)2: 3P,(1/2)3: 3P,(1/1+2)4: 3PN,(1/2)5: 3PN,(1/1+2) (*4)A.2.1.6 [D-01] R/W 0: No1: Open tariff2: Closed tariff3: ThermostatA.2.1.7 [C-07] R/W 0: LWT control1: Ext RT control2: RT controlA.2.1.8 [7-02] R/W 0: 1 LWT zone1: 2 LWT zonesA.2.1.9 [F-0D] R/W 0: Continuous1: Sample2: RequestA.2.1.A [E-04] R/O 0: No1: YesA.2.1.B R/W 0: At unit1: In room└─ OptionsA.2.2.1 [E-05] R/W 0: No (*1)1: Yes (*2)A.2.2.3 [E-07] R/W 0~60: Type 1 (*1)1: Type 2 (*2)A.2.2.4 [C-05] R/W 1: Thermo ON/OFF2: C/H requestA.2.2.5 [C-06] R/W 1: Thermo ON/OFF2: C/H requestA.2.2.6.1 [C-02] Digital I/O PCB Ext. backup heat src R/W 0: No1: Bivalent2: -3: -A.2.2.6.2 [D-07] Digital I/O PCB Solar kit R/W 0: No1: YesA.2.2.6.3 [C-09] Digital I/O PCB Alarm output R/W 0: Normally open1: Normally closedA.2.2.6.4 [F-04] Digital I/O PCB Bottom plate heater R/W 0: No1: YesA.2.2.7 [D-04] R/W 0: No1: Pwr consmp ctrlA.2.2.8 [D-08] R/W 0: No1: 0,1 pulse/kWh2: 1 pulse/kWh3: 10 pulse/kWh4: 100 pulse/kWh5: 1000 pulse/kWhA.2.2.9 [D-09] R/W 0: No1: 0,1 pulse/kWh2: 1 pulse/kWh3: 10 pulse/kWh4: 100 pulse/kWh5: 1000 pulse/kWhA.2.2.A [D-02] R/W 0~40: No1: Secondary rtrn2: Disinf. shuntA.2.2.B [C-08] R/W 0: No1: Outdoor sensor2: Room sensor└─ CapacitiesA.2.3.1 [6-02] R/W 0~10kW, step: 0,2kW3kW (*1)0kW (*2)A.2.3.2 [6-03] R/W 0~10kW, step: 0,2kW3kWA.2.3.3 [6-04] R/W 0~10kW, step: 0,2kW0kW (*3)6kW (*4)A.2.3.6 [6-07] R/W 0~200W, step: 10W0W└─ Space operation└─ LWT settings└────────────────── MainA.3.1.1.1 R/W 0: Fixed1: Weather dep.2: Fixed + scheduled3: WD + scheduledA.3.1.1.2.1 [9-01] Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C25°CA.3.1.1.2.2 [9-00] Temperature range Maximum temp (heating) R/W 37~depending on outdoor unit, step: 1°C55°CA.3.1.1.2.3 [9-03] Temperature range Minimum temp (cooling) R/W 5~18°C, step: 1°C5°CA.3.1.1.2.4 [9-02] Temperature range Maximum temp (cooling) R/W 18~22°C, step: 1°C22°CA.3.1.1.5 [8-05] R/W 0: No1: YesA.3.1.1.6.1 [F-0B] Shut-off valve Thermo On/OFF R/W 0: No1: YesA.3.1.1.6.2 [F-0C] Shut-off valve Cooling R/W 0: No1: YesA.3.1.1.7 [9-0B] R/W 0: Quick1: Slow└────────────────── AdditionalA.3.1.2.1 R/W 0: Fixed1: Weather dep.2: Fixed + scheduled3: WD + scheduledForced off contactEmitter typeLWT setpoint modeBooster heaterBUH: step 1BUH: step 2Bottom plate heaterLWT setpoint modeModulated LWTContact type add.Demand PCBExternal kWh meter 1External kWh meter 2DHW pumpExternal sensorPump operation modePower saving possibleUser interface locationDHW operationDHW tank typeContact type mainBUH typeUnit control methodNumber of LWT zones(*1) *HB*_(*2) *HV*_(*3) *3V_(*4) *9W_(*5) *04/08*_(*6) *11/16* 4P383508-1B - 2017.04