Field Setting SiBE811001EB107 CONVENI-PACK7. Field Setting7.1 Outdoor Unit(1) Setting by switchesThis unit has settings that can be made using the DIP switch and the BS button.The power must be turned OFF when setting the DIP switch, but must be turned ON when using the BS button.(Note there are 2 DIP switches, one is on the outdoor unit main PCB (inside right of the C/BOX) and the other is on thesub PCB (inside left of the C/BOX). Do not confuse these switches.)(2) DIP switch settings on the outdoor unit main PCB(3) Location of switches on the outdoor unit main PCB(4) Setting method of "Refrigeration forced ON" and "Air conditioning forced ON"DIP switch settings on themain PCBTarget evaporatingtemperature settingRefrigeration forcedOFF setting• When using this unit as a condensing unit, this switch sets the target evaporating temperature inincrements of 5˚C.(Factory setting: -10˚C)• This setting is used only when operating the air conditioning side of this unit. Set this DIP switch toOFF when reconnecting air conditioning equipment.(Factory setting: Refrigeration forced OFF is released)Air conditioning forcedOFF setting• This setting is used only when operating the refrigeration side of this unit. Set this DIP switch to OFFwhen reconnecting refrigeration equipment.Caution!: When operating in air conditioning forced run mode, DIP SW2 on the main PCB must be ON.(Factory setting: Air conditioning forced OFF is released )DS1C/BOX (right)DIP switchONOFF1 2 3 4 1 2 3 4DS2BS button (See following page for settings assignedto the BS button)• Target evaporatingtemperature setting• Air conditioningforced OFF setting• Refrigeration forcedOFF setting• Transmission-less settingNote) Do not move knobs DS1-4and DS2-4.Control board(main)Refrigeration forced OFFsetting (DS2-2) Air conditioning forced ONsetting (DS2-3)∗1) When refrigeration is set to forced OFF, it is necessary to set DS2 on themain PCB to ON. (The indoor unit is used for defrosting)Main DS2Refrigeration forced OFF isreleased (Factory setting)Main DS2Air conditioning forced OFF isreleased (Factory setting)Main DS2Refrigeration forced OFF (∗1)Main DS2Air conditioning forced OFF (∗1)ONOFF1 2 3 4ONOFF1 2 3 4ONOFF1 2 3 4ONOFF1 2 3 4