Standard Specification SiBE811001EB15 CONVENI-PACK3.1.2 Booster UnitNote+1 Operating conditions of booster unit: Evaporating temperature -35°C,outdoor temperature 32°C, Suction SH 10K,Saturated temperature to discharge pressure of booster unit -10°CModel LCBKQ3AV1LCBKQ3AV1(E)Power Supply 1 phase 220-240V 50HzCapacity 1 kW 3.35Range of Outdoor Temperature °C -15~+43Casing Color Ivory white (5Y7.5/1) [Light camel (2.5Y6.5/1.5)]Dimensions: (H×W×D) mm 480×680×310CompressorType Hermetically sealed swing typePiston Displacement m 3/h 10.16Number of Revolutions r.p.m 6540Motor Output × Number of Units kW 1.3Starting Method Direct-on-line (Inverter system)FanType Propeller fanAirflow Rate m 3/min 1.6Drive Direct driveConnectingPipesLiquid pipe For outdoor unit φ6.4 C1220T (Brazing connection)To indoor unit φ6.4 C1220T (Brazing connection)Gas pipe For indoor unit φ15.9 C1220T (Brazing connection)To outdoor unit φ9.5 C1220T (Brazing connection)Mass kg 47Safety Devices High Pressure Switch, Inverter Overload ProtectorRefrigerant Refrigerant Name R-410AControl Electronic Expansion ValveRefrigerantOilRefrigerant Oil Name DAPHNE FVC50K+FVC68DCharge Volume L 0.85+0.5Operating Sound dB(A) 49Standard Accessories Installation Manual, Clamping Materials, Hole Cap, Drain Socket, Drain Receiver